Water Flow - Balboa Clim8zone Installation Manual

Hide thumbs Also See for Clim8zone:
Table of Contents

Advertisement

22

WATER FLOW

THREE RULES OF WATER FLOW
FOR THE CLIM8ZONE
UNIT
TM
1
The CLIM8ZONE
unit (figure xx, A) should have an input water flow of 11.9 US
TM
GPM (45 LPM) +/- 10% for optimal efficiency when heating or cooling the water.
2
The water flow into the CLIM8ZONE
TM
unit should be greater than 3.57 US GPM
(13.5 LPM) to prevent a low flow error.
3
The water flow into the CLIM8ZONE
unit should be less than 17.8 US GPM to
TM
ensure the unit is not damaged over extended use.
CLIM8ZONE
Water Flow Rates
US Gallons Per Minute
TM
Optimal flow rate for heating/cooling
11.89
Maximum flow rate for heating/cooling (+10%)
13.08
Minimum flow rate for heating/cooling (-10%)
10.70
Maximum flow rate to prevent damage
17.83
Minimum flow rate to prevent low flow error
3.57
Water flow rate for the BP Control System:
Minimum: 23 GPM (5.22 m3/H)
The BP Control System has a minimum specified flow
rate of water through the electric heater for the BP
Control System to function properly. Therefore, a bypass
plumbing setup with slice values must be used in the hot
tub to allow for both the flow rate requirements of the
CLIM8ZONE
unit and the flow rate requirements of
TM
the BP Control System heater to be met in the hot tub.
The installer shall adjust the water flow into the
CLIM8ZONE
unit by using the ball valve to ensure that
TM
the flow rate is within the recommended ranges.
Low or No Flow Condition
The CLIM8ZONE
unit will shut itself off for safety
TM
reasons anytime the sensed water flow through the Heat
Pump falls below a threshold of 3.6 GPM (0.81 m3/h).
Balboa Water Group | Your Single Source Solution
Liter Per Minute
Meter
/Hour
3
45.0
2.70
49.5
2.97
40.5
2.43
67.5
4.05
13.5
0.81
During a Low/No Flow condition, the CLIM8ZONE
TM
unit will not heat or cool the water and will display an
error message on the control panel display.
High Temperature Safety Protection
The CLIM8ZONE
TM
unit will shut off all heating
or cooling for safety reasons anytime the water
temperature exceeds 43°C/109.4°F for 5 seconds at the
outlet or inlet.
Ozone / UV
Make sure any ozone / UV units are installed down
stream from the CLIM8ZONE
unit (Figure 9, F).
TM
HEATING PUMP & FLOW CONTROL VALVE
CONFIGURATION CHART
General Pump Type
HIGH Speed Amps
LOW Speed Amps
1.05A CIRC 60Hz
1.05
1.00A CIRC 60Hz
1.00
0.63A CIRC 60Hz
0.63
16/4 56 Frame 60Hz
16.4
4.8
16/4 56 Frame "Circ Killer" 60Hz
14
1. 1
12/2 56 Frame 60Hz
12. 1
2.0
12/4.4 56 Frame 60Hz
12
4.4
12/3.5 "XL" with Larger Impeller 60Hz
12
3.5
12/1 56 Frame "Circ Killer" 60Hz
12
1.0
10/3 48 Frame 60Hz
10.7
3.0
8.8/3 48 Frame 60Hz
8.8
3.0
73002: Flow Control Valve, High Amp
73003: Flow Control Valve, Low Amp
NO: Cannot use this pump
Patent Pending
Flow Control Valve
Flow Control Valve
Flow Control Valve
with 1.5" Plumbing
with 2" Plumbing
with 2.5" Plumbing
73002
73003
NO
73002
73003
NO
NO
73003
NO
NO
73002
73002
73002
73003
NO
NO
73002
73002
NO
73002
73002
NO
73002
73002
73002
73003
NO
NO
73002
73002
73002
73002
NO
FLOW CONTROL VALVE OPTIONS
Part number: 73002, High Amp (Patent Pending)
Part number: 73003, Low Amp (Patent Pending)
2.0"
Figure 10
INSTALLATION GUIDE
42391 Rev A
TM
23