Chapter 1 Safety Precautions 1.1 Before Power Up Danger Make sure the main circuit connections are correct. Single phase L1(L),L3(N), and Three phase L1(L),L2,L3(N); 400V : L1,L2,L3 are power-input terminals and must not be mistaken for T1,T2 and T3. Otherwise, inverter damage can result. Caution ...
1.3Before Operation Caution Make sure the model and inverter capacity are the same as that set in parameter 13-00. Note : On power up the supply voltage set in parameter 01-01 will flash on display for 2 seconds. 1.4 During Operation Danger ...
Chapter 2 Environment & Installation 2.1 System Diagram ~ ~ ~ Power supply: Power Supply Make sure the correct voltage is applied to avoid damaging the inverter. Molded Molded-case circuit breaker (MCCB) or fused disconnect: A molded-case circuit breaker or fused disconnect must be installed Circuit between the AC source and the inverter that conforms to the rated Breaker...
Page 5
2.2 Standard wiring Braking resistor (*1) Induction motor L1(L) Power source Power Inverter 1Φ:200-240V input output 3Φ:380-480V L3(N) Multi- Ground function Input Preset speed 250VAC/1A Relay (30VDC/1A) RESET output Common point for NPN Common point Safety for PNP terminal Pin1 to Pin8 Frequency 0-10V/4-20mA 1:Data+...
2.3 Terminal Description 2.3.1 Description of main circuit terminals Terminal symbols TM1 Function Description L1(L) Main power input Single phase: L1(L) / L3(N) Three phase: L1(L) / L2 / L3(N) L3(N) Externally connected braking resistor Inverter output, connect to U, V, W terminals of motor Ground terminal *P,BR is only for the model of frame 2.
Page 7
2.3.2 Description of control circuit terminals Terminal TM2 Function Description Signal Level symbols Relay output terminal, Specification: 250VAC/1A(30VDC/1A) 250VAC/1A(30VDC/1A) S1~S4 (common point) 【NPN】 ±15%,Max output current 30mA S1~S4 (common point) 【PNP】 SG(+24V) 24 VDC, 4.5 mA, optical coupling isolation S1~S4 Multi-function input terminals(refer to group3) (Max voltage30 VDC, Input impedance 6kΩ)
Page 8
2.4 Keypad Installation Description Keypad component: 1. Keypad 2. RJ45 Connector Keypad RJ45 Connector Keypad installation: →→ Follow the step Note: The RJ45 buckle must be inserted into the inverter. Keypad uninstallation: →→ Follow the step Scale 4:1...
Page 9
2.5 Grounding kit Installation Description When grounding kit installed: 1.Loose two screws of position 1 as figure a 2.Install two grounding kits in position 1 as figure b 3.Install two screws back of position 1 as figure c Notes: Please install the quantity of grounding kit according to actual usage.
Page 10
2.6 Din rail type Installation Description Assembly Steps: (1) Push the plastic base into the slot at the bottom of the heat sink of the machine by pressing the right arrow as shown in the figure. (2) Install the metal pressure plate and lock 6 fixing screws.
Chapter 3 Software Index 3.1 Programmable Parameter Groups Parameter Group No. Description Group F Simple function parameters Group 00 Basic parameters Group 01 V/F Pattern selections & setup Group 02 Motor parameters Group 03 Multi function digital Inputs/Outputs Group 04 Analog signal inputs/ Analog output Group 05 Preset Frequency Selections.
Page 12
Group F- Simple function parameters Group F- Simple function parameters group group Factory Factory No. Description Range Note No. Description Range Note Setting Setting Motor 0: Forward 8: Up Command rotation 1: Reverse 9: Down Command 0: Keypad Main Run 10: Second 1: External Source...
Page 13
Group F- Simple function parameters Group F- Simple function parameters group group Factory Factory No. Description Range Note No. Description Range Note Setting Setting xx0xx: Standard 20: Synchronize Motor xx1xx: Invertor 21: Synchronize Duty Motor 0: Reverse Reverse 22: Synchronize command is valid Operation 1: Reverse...
Page 14
Group 00- The basic parameters group Group 00- The basic parameters group Factory Factory No. Description Range Note No. Description Range Note Setting Setting Command 0: Forward/ Stop-Reverse/Stop Frequency 50.00/ 00-12 0.01~599.00 1: Run/ Upper Limit 60.00 Operation Stop-Reverse/For Frequency 00-13 0.00~598.99 0.00...
Page 15
Group 01- V/F Pattern selection & Setup Group 03- Multi function Digital Inputs/Outputs Factory No. Description Range Note Factory Setting No. Description Range Note Setting Curve 0: Forward/Stop Modification Command or Run (Torque /Stop Boost) Multifunction 1: Reverse/Stop V/F Start 01-11 0.00~10.00 0.00...
Page 16
Group 03- Multi function Digital Group 03- Multi function Digital Inputs/Outputs Inputs/Outputs Factory Factory No. Description Range Note No. Description Range Note Setting Setting Detection xxxx0:S1 NO Period xxxx1:S1 NC External xxx0x:S2 NO S1~ S4 Braking xxx1x:S2 NC 03-09 switch type 00000 03-17 0.00~20.00...
Page 17
Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections. Factory No. Description Range Note Setting Factory No. Description Range Note Preset Setting 05-25 Speed 10.0 0: Common 4-Acctime Accel/Decel Preset Accel/Decel 1 or 2 05-26 Speed 10.0 apply to all speeds Preset 4-Dectime Speed...
Page 18
Group 06- Auto Run(Auto Sequencer) Group 06- Auto Run(Auto Sequencer) function function Factory Factory No. Description Range Note No. Description Range Note Setting Setting Auto _ Run Auto_ Run Mode Mode 06-01 0.00 06-23 frequency running time command 1 setting 7 Auto _ Run Auto_ Run Mode...
Page 19
Group 07- Start/Stop command setup Group 08- Drive & Motor Protection functions Factory No. Description Range Note Setting Factory No. Description Range Note Direct 0: Enable Direct Setting Running run on power up x0xxx: Enable over 07-04 After Power 1: Disable Direct voltage Prevention run on power up in Run Mode...
Page 20
Group 08- Drive & Motor Protection Group 08- Drive & Motor Protection functions functions Factory Factory No. Description Range Note No. Description Range Note Setting Setting 2: Motor Overload 0: AVR function Protection Level 2 enable 1: AVR function Disable 2: AVR function disable for stop 3: AVR function...
Page 21
Group10- PID function Setup Group10- PID function Setup Factory Factory No. Description Range Note No. Description Range Note Setting Setting 0: Reserved 1: Negative PID target 1: Analog Signal PID Offset value 10-09 0 ~ 109 Input. (AVI/ACI) Adjust selection 2: Reserved PID Output (when...
Page 22
Group11- Performance Control Group11- Performance Control functions functions Factory Factory No. Description Range Note No. Description Range Note Setting Setting 0: Reverse 0: Enable Stop Key command is when Run Reverse enabled Command not from 11-00 operation 1: Reverse Stop Key Keypad control 11-21...
Group12 Digital Display & Monitor Group 13 Inspection & Maintenance functions functions Factory Factory No. Description Range Note No. Description Range Note Setting Setting 1150: Initialization Inputs and (50Hz,220V/380V) output 1160: Initialization Logic status 12-05 ----- (60Hz,220V/380V) display 1250: Initialization ( S1 to S5) &...
Page 24
Faults which cannot be recovered Faults which can be recovered manually manually and automatically Display Corrective action Display Corrective action time CtEr 2.Consider use of a brake Consult with the supplier resistor and/or brake module (For 400V Check the inverter HPErr models or 200V capacity setting (13-00) to...
Page 25
4.1.2 Keypad Operation Error Display Description external terminal control Instruction mode (00-02/00-03=1) and Display Corrective action direct start is disabled (07-04=1) 1.Adjust 13-06 2. The inverter cannot be 2.Adjust 11-00 started and will flash STP1. 1.The ▲ or▼ is available Err1 3.
Page 48
Appendix-2 Instructions for UL Appendix Instructions for UL ◆ Safety Precautions DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. WARNING Electrical Shock Hazard Do not operate equipment with covers removed.
Page 49
Failure to comply could result in damage to the drive and will void warranty. Teco is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices.
Page 50
Appendix Instructions for UL ■ Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, 75 °C cooper wire are to be used。 ...
Page 51
Appendix Instructions for UL ◆ Drive Motor Overload Protection Set parameter 02-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC. ■...
Page 52
Préface Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement. Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié...
1.2 Câblage Avertissement Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs. Le câblage doit être effectué par un personnel qualifié / électricien certifié. Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance ...
pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. Ne pas brancher ou débrancher le moteur pendant le fonctionnement. Le variateur pourrai se déclencher et ainsi endommager le lecteur. Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé...