Xylem Bell & Gossett ecocirc XL Series Instruction Manual page 10

Hide thumbs Also See for Bell & Gossett ecocirc XL Series:
Table of Contents

Advertisement

Available languages

Available languages

1. Open the terminal box cover removing the screws (5). Refer to fig-
ures 2 & 3 on page 7. Use control screwdriver described under sec-
tion 4.2 to access terminal blocks.
2. Connect the appropriate wires according to the terminal block dia-
gram and the requirements of section
page 9 given below in section 4.7.3.
3. Close the terminal box cover.
4.7.3 Connection assignment
• For all electrical connections, use heat resistant wires or cable that is
rated for at least 194°F (90°C). Make sure that the wiring does not
touch the motor housing, the pump, or the piping.
• Power and control wires must be run in separate channels.
• Metal conduit for power wiring must only be attached to 1/2" NPT
conduit fitting.
• For a two-pump connection, wire both pumps through a communi-
cation cable connecting the 2 RS-485 ports at the pumps to termi-
nals 15, 16 & 17 for single phase pumps and 5–6 & 7 for three phase
pumps.
• Low voltage wiring is recommended to be twisted pair and shield-
ed. Sensor wiring is not to exceed 65 feet (19.8 m).
NOTICE:
Cable glands are only available for low voltage wiring to protect
against cable slippage and vapor ingress into the terminal box.
5 System Description
5.1 User interface
5
7
8
6
9
Figure 8: User interface diagram for single phase models
6
7
8
9
4
3
1
Figure 9: User interface diagram for three phase models
1. Control mode button
2. Control mode indicators
3. Parameter button
4. Parameter indicators
5. Setting buttons
6. Numeric display
ecocirc
®
XL INSTRUCTION MANUAL
Connection assignment
4
3
2
1
5
2
7. Power indicator
8. Status / Fault indicator
9. Remote control indicator
Hot Surface:
on
Burn hazard. During normal operation, the pump surfaces
may be so hot that only the buttons should be touched to
avoid burns.
5.1.1 User interface locking/unlocking
The user interface will automatically lock if no button is pressed for ten
minutes, or if the upper setting button (5) and the parameter button (3)
are pressed for two seconds. See
If a button is pressed when the user interface is locked, the display (6)
shows:
To unlock the user interface, press the upper setting button (5) and the
parameter button (3) for two seconds. The display (6) will show:
Now it is possible to change the pump setting as required.
5.2 Functions
The main functions of the pump and control modes are selectable
through the pump user interface and the embedded I/O. Advanced
functions or communication features, can only be set via bus protocol
or the optional Wireless module. See the electronic drive manual at
www.bellgossett.com.
5.2.1 Control mode
Mode
Constant pressure
Hset
Proportional pressure
Hset
Hset
2
Fixed speed control
Max
Speed
setpoint
min
All the above control modes can be combined with the night mode
function.
5.2.2 Night mode
The night mode cannot be used in cooling systems.
Prerequisite
• The pump is installed between boiler outlet and system supply.
• The night mode feature is initiated when the pump recognizes a wa-
ter temperature change brought about by the boiler or high level
control system.
5 System Description
User interface
on page 9.
Description
The pump maintains a constant
pressure at any flow demand. The
desired head of the pump can be
set via user interface. See section
6.1.2 Change set point.
The pump pressure is continuous-
ly increased/decreased depend-
ing on the increased/decreased
flow demand. The maximum head
of the pump can be set via user in-
terface. See section 6.1.2 Change
set point.
The pump maintains a fixed speed
at any flow demand. The speed of
the pump can be set via user inter-
face. See section 6.1.2 Change set
point.
9

Advertisement

Table of Contents
loading

Table of Contents