Safety Components - Riello RLS 1600/E C11 Modulating Operation

Dual fuel light oil/gas burners
Table of Contents

Advertisement

GAS OPERATION
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
EN 676
Max. output
Theoretical max
CO
GAS
2
0 % O
2
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
Air excess
Max. output
  1.2
  1.3
CO
% Calibration
2
mg/kWh
 = 1.3
 = 1.2
9.7
9
9.5
8.8
11.6
10.7
11.4
10.5
Maintenance
7.2.4

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. O. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
CO
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid)
(if present)
 100
Oil regulator (if present)
 100
 100
Oil pipes / couplings
(metallic) (if present)
 100
Tab. N
Flexible hoses (if present)
Fan impeller
37
GB
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000 pressurised
cycles
10 years or 500,000 start-ups
Tab. O
20099672