Calibration Of The Thermal Relay - Riello RLS 1600/E C11 Modulating Operation

Dual fuel light oil/gas burners
Table of Contents

Advertisement

5.17

Calibration of the thermal relay

The thermal relay (Fig. 34) serves to avoid damage to the motor
due to an excessive absorption increase or if a phase is missing.
For calibration 2), refer to the table indicated in the electrical lay-
out (electrical wiring in charge of the installer).
To reset, in case of an intervention of the thermal relay, press but-
ton "RESET" 1).
The button "STOP" 3) opens the NC contact (95-96) and stops
the motor.
Insert a screwdriver in the window "TEST/TRIP" 4) and move it in
the arrow direction (to the right) to carry out the thermal relay test.
The burner leaves the factory set for the 5.5 kW pump motor.
Adjust the relay according to the output of the pump that will
be installed.
The automatic reset can be dangerous.
This operation is not foreseen in the burner oper-
ation.
WARNING
Installation
D11301
29
GB
Fig. 34
20099672

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 2000/e c112008087020080864

Table of Contents