5.4
Operating position
The burner is designed to operate only in
positions 1 and 4 (Fig. 11).
Installation 1 is preferable, as it is the only
one that allows the maintenance operations
WARNING
as described in this manual.
Installation 4 permits operation but make
maintenance and inspection of the combus-
tion head more difficult.
Any other position could compromise the cor-
rect operation of the appliance.
Installations 2, 3 and 5 are prohibited for
safety reasons.
DANGER
5.5
Removing the shutter lockout screws
Remove the screws 1)-2) and nuts before fitting the burner onto
the boiler (Fig. 12). Replace them with the screws 3) M12x16
supplied as standard.
5.6
Coupling of the burner - Centre of gravity position
Provide an adequate lifting system.
20099672
Installation
1 0 7
1
2
20124105
Hook and lift the burner as shown in Fig. 13
WARNING
1 8 0
20124106
18
GB
3
4
1
3
2
3
20094549
2
1
5
Fig. 11
Fig. 12
Fig. 13