4.8

Firing rates

The MAXIMUM OUTPUT is chosen from within the continuous
diagram area (Fig. 3).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
RLS 1600/E C11 = 3065 kW
RLS 2000/E C11 = 4000 kW
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
0
1000
2000
3000
4.9

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 4).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the manufac-
turer. The firing rates were set in relation to special test boilers,
according to EN 676 regulations.
20099672
Technical description of the burner
5000
8000
4000
6000
7000
Thermal power – kW
The firing rate value (Fig. 3) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1,013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
WARNING
shown on page 22.
RLS 1600/E
10000 11000
12000 13000
9000
In Fig. 4 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 7000 kW - diameter 120 cm - length 6 m
MODULATING RATIO
The modulating ratio, obtained in the test boilers, according to
standard (EN 676 for gas, EN 267 for light oil), is of 4:1.
10
GB
RLS 2000/E
14000
15000 16000 17000 18000 19000
D2448
20124102
20000
21000
Fig. 3
Fig. 4