Connecting the solar control unit
The following cables/leads have yet to be connected to
the Vitosolic 100 or the SDIO/SM1A electronics mod-
ule:
Power supply
■
■
Collector temperature sensor
■
Connection to Vitotronic boiler control units (KM-
BUS) or PlusBus
!
Please note
Routing 230 V cables immediately adjacent to
extra low voltage (ELV) leads may lead to data
being corrupted during transmission.
Route extra low voltage (ELV) leads < 42 V and
cables
230 V~ separately underneath the
≥
cover of the DHW cylinder.
Connecting the immersion heater EHE
Immersion heater EHE installation instructions
Connecting the heating water side and solar side
Connect all pipework with detachable fittings.
■
■
Seal connections that are not required with caps.
■
Adjust the high limit safety cut-out so that the DHW
temperature in the DHW cylinder does not exceed
95 °C.
Permissible temperatures
Solar side
Heating water side
Permissible operating pressure
Solar side
Heating water side
Test pressure
Solar side
Heating water side
System scheme with solar collectors and boiler
■
Heating of DHW by solar collectors via the lower
internal indirect coil
■
Heat supply for reheating or heating DHW with a
boiler via the upper internal indirect coil
16
(cont.)
Vitosolic 100 or SDIO/SM1A electronics module
installation and service instructions
Solar collector installation instructions
Note
Vitosol collectors can be operated with up to 6 bar
(0.6 MPa).
160 °C
160 °C
10 bar
(1.0 MPa)
10 bar
(1.0 MPa)
16 bar
(1.6 MPa)
16 bar
(1.6 MPa)