CHILLER ALERTS
ICVC FAULT
PRIMARY
STATE
MESSAGE
140
SENSOR ALERT
141
SENSOR ALERT
142
LOW OIL
PRESSURE ALERT
143
AUTORESTART
PENDING
144
AUTORESTART
PENDING
145
AUTORESTART
PENDING
146
AUTORESTART
PENDING
147
AUTORESTART
PENDING
148
AUTORESTART
PENDING
149
SENSOR ALERT
150
SENSOR ALERT
151
CONDENSER
PRESSURE ALERT
152
RECYCLE ALERT
153
no message:
ALERT
only
154
POTENTIAL
FREEZE-UP
155
OPTION SENSOR
FAULT
156
OPTION SENSOR
FAULT
157
OPTION SENSOR
FAULT
158
SENSOR ALERT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 4 — ICVC Alert Codes (cont)
SECONDARY
MESSAGE
LEAVING COND WATER
140Sensor Fault: Check
TEMP
Leaving Cond Water Sensor.
ENTERING COND WATER
141Sensor Fault: Check
TEMP
Entering Cond Water Sensor.
CHECK OIL FILTER
142Low Oil Pressure Alert.
Check Oil Filter.
LINE CURRENT
143Line Current Imbal-
IMBALANCE
ance: Check VFD Fault His-
tory for Values.
LINE VOLTAGE
144Single Cycle Line
DROP OUT
Voltage Dropout.
HIGH LINE VOLTAGE
145High Percent Line
Voltage [VALUE].
LOW LINE VOLTAGE
146Low Percent Line
Voltage [VALUE].
VFD MODULE RESET
147->VFD Module Power-On
Reset When Running.
POWER LOSS
148Control Power-Loss
When Running.
HIGH DISCHARGE TEMP 149Comp Discharge Temp
[VALUE] Exceeded Limit of
[LIMIT]*.
HIGH BEARING
150Comp Thrust Brg Temp
TEMPERATURE
[VALUE] exceeded limit of
[LIMIT]*.
PUMP RELAY
151High Condenser Pres-
ENERGIZED
sure [VALUE]: Pump Ener-
gized to Reduce Pressure.
EXCESSIVE RECYCLE
152Excessive recycle
STARTS
starts.
no message; ALERT only
153Lead/Lag Disabled-
Config: Duplicate Chiller
Address.
COND PRESS/TEMP
154Condenser freeze up
TOO LOW
prevention.
REMOTE RESET
155Sensor Fault/Option
SENSOR
Disabled: Remote Reset
Sensor.
AUTO CHILLED WATER
156Sensor Fault/Option
RESET
Disabled: Auto Chilled Water
Reset.
AUTO DEMAND LIMIT
157Sensor Fault/Option
INPUT
Disabled: Auto Demand Limit
Input.
SPARE TEMPERATURE
158Spare Temperature 1
#1
[VALUE] exceeded limit of
[LIMIT]*.
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.
Power loss has been detected in any phase.
Chiller automatically restarting.
A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically restarting if Auto Restart is
enabled in OPTIONS screen.
Check phase to phase and phase to ground line
power.
Check phase to phase and phase to ground line
power.
VFD Module has detected a hardware fault due
to electrical noise, power loss or software and
has reset. Chiller automatically restarting.
Check for power loss and sources of electro-
magnetic interference.
Check 24 vac control power supply to ICVC.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for fouled tubes or noncondensables in
the chiller.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil temperature.
Check sensor wiring and accuracy.
Check condenser flow and water temperature.
Check for fouled tubes.
This alarm is not caused by the High Pressure
Switch.
Chiller load is too low to keep compressor on
line and there has been more than 5 starts in
4 hours.
Increase chiller load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T from
SETUP1 Screen.
Illegal chiller address configuration in Lead/Lag
screen. Both chillers require a different address.
The condenser pressure transducer is reading a
pressure that could freeze the condenser tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN mode if the
vessel is evacuated.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.
Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #1 Limit in SETUP1 screen.
13
ADDITIONAL CAUSE/REMEDY