Icvc Alarm Codes - Carrier 19XRV Start-Up And Service Instructions

With pic iii controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

CHILLER PROTECTIVE LIMIT FAULTS
ICVC FAULT
PRIMARY
STATE
MESSAGE
200
PROTECTIVE LIMIT RECTIFIER POWER
201
PROTECTIVE LIMIT INVERTER POWER FAULT 201Inverter Power Fault:
202
PROTECTIVE LIMIT MOTOR AMPS NOT
203
FAILURE TO START MOTOR ACCELERATION
204
FAILURE TO STOP
205
PROTECTIVE LIMIT HIGH DC BUS VOLTAGE
206
PROTECTIVE LIMIT VFD FAULT
207
PROTECTIVE LIMIT HIGH CONDENSER
208
PROTECTIVE LIMIT EXCESSIVE MOTOR
209
PROTECTIVE LIMIT LINE CURRENT
210
PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210Single Cycle Line Volt-
211
PROTECTIVE LIMIT HIGH LINE VOLTAGE
212
PROTECTIVE LIMIT LOW LINE VOLTAGE
213
PROTECTIVE LIMIT VFD MODULE RESET
214
PROTECTIVE LIMIT POWER LOSS
215
PROTECTIVE LIMIT LOW DC BUS VOLTAGE
216
PROTECTIVE LIMIT LINE VOLTAGE
217
PROTECTIVE LIMIT MOTOR OVERLOAD TRIP 217Motor Overload Trip;
218
PROTECTIVE LIMIT VFD RECTIFIER
219
PROTECTIVE LIMIT VFD INVERTER
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
NOTE: ICVC Alarms 212-226 are declared as a result of VFD Faults.
Table 5 — ICVC Alarm Codes
SECONDARY
MESSAGE
200Rectifier Power Fault:
FAULT
Check VFD Status.
Check VFD Status.
202Motor Amps Not
SENSED
Sensed — Average Load
Current [VALUE].
203Motor Acceleration Fault
FAULT
— Average Load Current
[VALUE].
VFD SHUTDOWN FAULT
204VFD Shutdown Fault:
Check Inverter Power Unit.
205High DC Bus Voltage:
[VALUE] exceeded limit of
[LIMIT]*.
206VFD Fault Code:
[VALUE]; Check VFD Fault
Code List.
207High Cond Pressure
PRESSURE
trip. [VALUE] exceeded Switch
Trippoint.
208Percent Load Current
AMPS
[VALUE] exceeded limit of
[LIMIT]*.
209Line Current Imbal-
IMBALANCE
ance: Check VFD Fault His-
tory for Values.
age Dropout.
211High Percent Line Volt-
age [VALUE].
212Low Percent Line Volt-
age [VALUE].
213VFD Module Power-On
Reset When Running.
214Control Power Loss
When Running.
215Low DC Bus Voltage:
[VALUE] exceeded limit of
[LIMIT]*.
216Line Voltage Imbal-
IMBALANCE
ance. Check VFD Fault His-
tory for Values.
Check VFD configurations.
218VFD Rectifier Temp
OVERTEMP
Exceeded: Check Cooling and
VFD Config.
219VFD Inverter Temp
OVERTEMP
Exceeded: Check Cooling and
VFD Config.
PRIMARY CAUSE
Malfunction within VFD Power Module.
Call Carrier Service.
Malfunction within VFD Power Module.
Call Carrier Service.
Check main circuit breaker for trip. Increase
Current % Imbalance in VFD_CONF screen.
Check that inlet guide vanes are fully closed at
start-up.
Check Motor Rated Load Amps in VFD_CONF
screen. Reduce unit pressure if possible.
VFD Circuit Board malfunction.
Call Carrier Service.
Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient volt-
age conditions. VFD Circuit Board malfunction.
Call Carrier Service.
See VFD Fault Code description and corrective
action.
Check Compressor Discharge High Pressure
switch wiring and accuracy.
Check for high condenser water temperatures,
low water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables in refrigerant.
Check Motor Rated Load Amps in VFD_CONF
screen. Percent Load Current > 110%.
Check Motor Rated Load Amps setting.
Check phase to phase and phase to ground
power distribution bus voltage.
Check Line Current % Imbalance in VFD_CONF
screen. Consult power company.
Temporary loss of voltage. Disable Single Cycle
Dropout in VFD_CONF screen.
Check phase to phase and phase to ground dis-
tribution bus voltage. Consult power company.
Check phase to phase and phase to ground dis-
tribution bus voltage. Consult power company.
Temporary loss of VFD control voltage. Check
VFD control power breaker, transformer and
fuses.
Check phase to phase and phase to ground dis-
tribution bus voltage.
Check VFD fuses.
Check 24 vac power supply to ICVC.
Consult power company.
Verify phase-to-phase and phase-to-ground line
voltage. VFD Circuit Board malfunction.
Call Carrier Service.
Check phase-to-phase and phase-to-ground
distribution bus voltage. Increase Line Voltage
% Imbalance in VFD_CONF screen.
Any phase current > 106% Rated Load Amps.
Can result from significant load side current
imbalance when running at full load.
Check entering condenser water temperature
and water flow rate.
Check Motor Rated Load Amps in VFD_CONF
screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation and
blockage.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation and
blockage.
15
ADDITIONAL CAUSE/REMEDY