APPENDIX B
POINT DESCRIPTION
1st Current Alarm State
Active Demand Limit
Actual Guide Vane Position
Actual VFD Speed
Calc Evap Sat Temp
Chilled Water Deadband
Chilled Water Delta P
Chilled Water Delta T
Chilled Water Pump
Chilled Water Temp
Chiller Start/Stop
Comp Discharge Temp
Comp Motor Winding Temp
Comp Thrust Brg Temp
Cond Water Flow
Cond Water Pump
Condenser Pressure
Condenser Refrig Temp
Condenser Water Delta P
Control Point
Current CHW Setpoint
Demand Level 1
Demand Level 2
Demand Level 3
Element Comm Status
Element Communications
Alarm
Emergency Stop
Entering Chilled Water
Entering Condenser Water
Equipment Alarm
Evaporator Pressure
Evaporator Refrigerant Temp
Leaving Chilled Water -
Prime Variable
Leaving Condenser Water
Line Active Current
Line Active Voltage
Line Frequency
Line Power Factor
Local Schedule
Occupied?
Oil Sump Temperature
Remote Start Contact
Run Status
Service Ontime
Surge Line Delta T
System Alert/Alarm
— OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List
CCN
READ/
UNITS
POINT NAME
WRITE
ALARM_01
R
DEM_LIM
R/W
%
GV_POS
R
%
VFD_ACT
R
%
EAT
R
°F
CWDB
R
^F
CHWPD
R
^F
CHW_DT
R
^F
CHLP
R
N/A
CHW_TMP
R
°F
CHIL_S_S
R/W
N/A
CMPD
R
°F
MTRW
R
°F
MTRB
R
°F
CDW_FLOW
R
N/A
CDP
R
N/A
CRP
R
PSI
CRT
R
°F
CDWPD
R
PSI
LCW_STPT
R/W
°F
CHWSTPT
R
°F
N/A
R
%
N/A
R
%
N/A
R
%
N/A
R
N/A
N/A
R
N/A
EMSTOP
R
N/A
ECW
R
°F
ECDW
R
°F
N/A
R
N/A
ERP
R
PSI
ERT
R
°F
LCW
R
°F
LCDW
R
°F
AMPS_ACT
R
A
VOLT_ACT
R
V
LINEFREQ
R
Hz
LINE_PF
R
N/A
R
N/A
OCC
R
N/A
OILT
R
°F
REM_CON
R/W
N/A
STATUS
R
N/A
S_HRS
R/W
hr
DELTA_TX
R
°F
SYS_ALM
R
N/A
DEFAULT
RANGE
VALUE
N/A
0-270
N/A
40 to 100
N/A
0 to 100
N/A
0 to 110
N/A
-40 to 245
1.0
0.5 to 2.0
N/A
-6.7 to 420
N/A
-40 to 245
OFF
OFF/ON
N/A
-40 to 245
STOP
STOP/START
N/A
-40 to 245
N/A
-40 to 245
N/A
-40 to 245
NO
NO/YES
OFF
OFF/ON
N/A
-6.7 to 420
N/A
-40 to 245
N/A
-6.7 to 420
N/A
10 to 120
N/A
0.00 to 99.9
N/A
0 to 100
N/A
0 to 100
N/A
0 to 100
N/A
No Comm/Normal
N/A
Inactive/Active
ENABLE/
ENABLE
EMSTOP
N/A
-40 to 245
N/A
-40 to 245
Comm Normal
N/A
Comm Lost
N/A
-6.7 to 420
N/A
-40 to 245
N/A
-40 to 245
N/A
-40 to 245
N/A
0.0 to 99999.0
N/A
0.0 to 99999.0
N/A
0 to 99
N/A
0.00 to 2.00
N/A
No Comm/Normal
NO
NO/YES
N/A
-40 to 245
OPEN
OPEN/CLOSE
0=Timeout,
1=Ready,
2=Recyle,
3=Startup,
4=Running,
5=Demand,
6=Ramping,
N/A
7=Autorest,
8=Override,
9=Tripout,
10=Control Test,
11=Lockout,
12=Pumpdown,
13=Prestart
N/A
0 to 32767
N/A
0 to 200
1=Normal,
N/A
2=Alert, 3=Alarm
37
BACNET
BACNET
OBJECT ID
OBJECT NAME
AV:4
alarm_01_1
AV:6
dem_lim_1
AV:7
gv_pos_1
AV:11
vfd_act_1
AV:13
ert_1
AV:14
cwdb_1
AV:15
chwpd_1
AV:16
chw_dt_1
BV:4
chlp_1
AV:17
chw_tmp_1
BV:5
chil_s_s_1
AV:18
cmpd_1
AV:19
mtrw_1
AV:20
mtrb_1
BV:6
cdw_flow_1
BV:7
cdp_1
AV:21
crp_1
AV:22
crt_1
AV:23
cdwpd_1
AV:24
lcw_stpt_1
AV:25
chwstpt_1
AV:1
dmv_lvl_1_perct_1
AV:2
dmv_lvl_2_perct_1
AV:3
dmv_lvl_3_perct_1
BV:2999
element_stat_1
BV:20
comm_lost_alm_1
BV:8
emstop_1
AV:26
ecw_1
AV:27
ecdw_1
BV:1
element_alarm_1
AV:28
erp_1
AV:13
ert_1
AV:31
lcw_1
AV:32
lcdw_1
AV:8
amps_act_1
AV:9
volt_act_1
AV:30
linefreq_1
AV:34
line_pf_1
BV:2
schedule_1
BV:10
occ_1
AV:33
oilt_1
BV:11
rem_con_1
AV:35
status_1
AV:36
s_hrs_1
AV:38
delta_tx_1
AV:40
sys_alm_1
611