Carrier 19XRV Start-Up And Service Instructions page 9

With pic iii controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

NAME
COLOR
Green
Yellow
Red
STS (Status)
Red/Yellow
Green/Red
None (Unlit)
Red
ENET
Red/Green
Green
None (Unlit)
LINK
Green
NOTES:
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms
are user configurable.
VERIFYING THAT DC BUS CAPACITORS ARE DIS-
CHARGED — The drive's DC bus capacitors retain hazard-
ous voltages after input power has been disconnected. Perform
the following steps before touching any internal components:
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive's input power
terminals.
3. Measure the DC bus potential with a voltmeter while
standing on a non-conductive surface and wearing insu-
lated gloves (1000 V). Measure the DC bus potential. See
Fig. 5 for the 248-amp drive and Fig. 6 for the 361 and
477-amp drives. The voltage between DC+ and DC-, and
from each DC terminal to the chassis must be zero before
proceeding.
4. Once the drive has been serviced, reapply input power.
HIGH TEMPERATURE ALARMS —
through the cold plate is controlled by an orifice in the refriger-
ant line leaving the cold plate. The orifice looks like one of the
O-ring face seal connectors and in fact is used as one of the
connections on the coolant tubing. The difference is that the
passage through the fitting is 0.375 in. (9.5 mm). If the orifice
is present and condenser liquid flow is present, the liquid will
flash to cooler temperature at the orifice. This temperature dif-
ference is great enough to be easily felt.
MAIN CONTROL BOARD (MCB) COMPONENTS —
Figure 13 shows the drive module with the cover removed. To
access the control boards, loosen the screw on the face of the
keypad mount and swing the keypad mount upward.
The components on the main control board (MCB) are
shown in Fig. 14. Note the location of the terminals labeled
MCB I/O. The high pressure switch is wired to these terminals
as shown in Fig. 15. In the event of a high condenser pressure
alarm, the connections at these terminals should be checked
and tightened if necessary.
A typical wiring schematic is shown in Appendix A.
Table 3
Drive Status Indicator Descriptions
STATE
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Flashing
Drive is not running. A type 2 (non-configurable) alarm condition exists and the
drive cannot be started.
Steady
Drive is not running, a type 1 alarm condition exists. The drive can be started.
Flashing
A major fault has occurred. Drive cannot be started until fault condition is
cleared.
Steady
A non-resettable fault has occurred.
Flashing Alternately
A minor fault has occurred. When running, the drive continues to run. System is
brought to a stop under system control. Fault must be cleared to continue. Use
parameter 950 [Minor Flt Config] to enable. If not enabled, acts like a major
fault.
Flashing Alternately
Drive is flash updating.
Off
Adapter and/or network is not powered, adapter is not properly connected to
the network, or adapter needs an IP address.
Flashing
An EtherNet/IP connection has timed out.
Steady
Adapter failed the duplicate IP address detection test.
Flashing Alternately
Adapter is performing a self-test.
Flashing
Adapter is properly connected but is not communicating with any devices on
the network.
Steady
Adapter is properly connected and communicating on the network.
Off
Adapter is not powered or is not transmitting on the network.
Flashing
Adapter is properly connected and transmitting data packets on the network.
Steady
Adapter is properly connected but is not transmitting on the network.
Coolant flow
9
DESCRIPTION
2. A Type 2 alarm indicates that a configuration error exists and
the drive cannot be started. Type 2 alarms are not configurable.
Fig. 13 — Drive Module with Cover Removed
SWING UP KEY PAD
MOUNT TO ACCESS
CONTROL BOARDS
a19-1843