Carrier 19XRV Start-Up And Service Instructions page 19

With pic iii controls rockwell powerflex 755 vfd option
Table of Contents

Advertisement

CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
PRIMARY
STATE
MESSAGE
259
PROTECTIVE LIMIT CCN OVERRIDE STOP
282
PROTECTIVE LIMIT INVALID VFD CONFIG
283
PROTECTIVE LIMIT INVALID VFD CONFIG
284
VFD GATEWAY
285
VFD GATEWAY
286
PROTECTIVE LIMIT INVERTER
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
OUT-OF-RANGE SENSOR
ICVC FAULT
PRIMARY
STATE
MESSAGE
260
SENSOR FAULT
261
SENSOR FAULT
262
SENSOR FAULT
263
SENSOR FAULT
264
SENSOR FAULT
265
SENSOR FAULT
266
SENSOR FAULT
267
SENSOR FAULT
268
SENSOR FAULT
269
SENSOR FAULT
270
SENSOR FAULT
271
SENSOR FAULT
Table 5 — ICVC Alarm Codes (cont)
SECONDARY
MESSAGE
259CCN Emergency/
Override Stop.
282Line Frequency
[VALUE] Exceeded Configura-
tion Range.
283Compressor 100%
Speed Config Ranges: 50=Hz
45-52; 60 Hz=55-62.
COMPATIBILITY
284VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/
VFD Versions.
COMPATIBILITY
285VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/
ICVC Versions.
286Inverter Overcurrent
OVERCURRENT
Fault: Check VFD Status.
SECONDARY
MESSAGE
LEAVING CHILLED WATER 260Sensor Fault: Check
Leaving Chilled Water Sensor.
ENTERING CHILLED
261Sensor Fault: Check
WATER
Entering Chilled Water
Sensor.
CONDENSER PRESSURE 262Sensor Fault: Check
Condenser Pressure Sensor.
EVAPORATOR
263Sensor Fault: Check
PRESSURE
Evaporator Pressure Sensor.
COMPRESSOR BEARING
264Sensor Fault: Check
TEMP
Comp Thrust Brg Temp Sensor.
COMPRESSOR MOTOR
265Sensor Fault: Check
TEMP
Comp Motor Winding Temp
Sensor.
COMP DISCHARGE TEMP 266Sensor Fault: Check
Comp Discharge Temp Sensor.
OIL SUMP TEMP
267Sensor Fault: Check Oil
Sump Temp Sensor.
COMP OIL PRESS DIFF
268Sensor Fault: Check Oil
Pump Delta P Sensor.
CHILLED WATER FLOW
269Sensor Fault: Check
Chilled Water Delta P Sensor.
COND WATER FLOW
270Sensor Fault: Check
Cond Water Delta P Sensor.
EVAP SATURATION TEMP
271Sensor Fault: Check
Evap Saturation Temp Sensor.
PRIMARY CAUSE
CCN has signaled the chiller to stop.This fault
must be manually reset from the default screen
of the ICVC.
LINE FREQUENCY in POWER screen must be
maintained between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). LINE FRE-
QUENCY must be maintained between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
Check high pressure switch and connections to
TB4-24 and TB4-25.
COMPRESSOR 100% SPEED in VFD_CONF
screen must be set between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). COMPRES-
SOR 100% SPEED must be set between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
VFD Gateway and VFD software versions are
not compatible.
Call Carrier Service.
VFD Gateway and ICVC software versions are
not compatible.
Call Carrier Service.
Check for high entering water temperature or
low condenser water flow.
Check current settings in VFD_CONF screen.
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor wiring.
Check for disconnected or shorted wiring.
Check for condensation in transducer
connector.
Check sensor wiring.
Check for disconnected or shorted wiring.
Check for condensation in transducer
connector.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
Check sensor wiring and accuracy.
Check for disconnected or shorted wiring.
If pressure transducers are not installed,
check for presence of resistors and jumpers
on lower CCM terminal block J3.
Check sensor wiring and accuracy.
Check for disconnected or shorted wiring.
If pressure transducers are not installed,
check for presence of resistors and jumpers
on lower CCM terminal block J3.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for disconnected or shorted wiring.
19
ADDITIONAL CAUSE/REMEDY
ADDITIONAL CAUSE/REMEDY