System Sizing; System And Rectifier Selection - Eaton SC200 Installation And Operation Manual

Hide thumbs Also See for SC200:
Table of Contents

Advertisement

4
A
p
p
e
n
d
i
x
C

System Sizing

System and Rectifier Selection

Follow these steps to select the correct system model, rectifier type and number of rectifiers
for your application:
What is the nominal ac supply voltage (120V or 208-240V)?
1
What is the total power requirement of the equipment to be connected to the
2
EPS2/EPS5?
Add up the power ratings of all equipment that will be powered from the
EPS2/EPS5. Look at the rating labels on the back of the routers, servers and other
equipment. Or refer to the equipment manufacturer's specifications. The power is
given in watts (W).
If you plan to add more equipment later then you may want to size the EPS2/EPS5
so that it can also supply this future requirement.
Up to 10 dc circuits can be connected to each EPS2/EPS5.
Select the EPS2/EPS5 system and rectifier type to suit your needs.
3
Use one of the selection charts below to select the correct system and rectifier type.
The number of rectifier modules shown in the charts includes one redundant
rectifier. This is an additional (hot-spare) rectifier for added security.
Supply Voltage: 120V ac
Connectable Equipment Power (W):
System model:
Rectifier type:
Number of rectifiers:
Supply Voltage: 208-240V ac
Connectable Equipment Power (W):
System model:
Rectifier type:
Number of rectifiers:
EPS2
EPR48-3G APR48-3G EPR48-3G EPR48-3G
EPS2
EPR48-3G APR48-3G EPR48-3G EPR48-3G
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C
System Sizing
550
1100
1100
EPS2
EPS5
2
2
900
1800
1800
EPS2
EPS5
2
2
September 2008
Appendix C
1650
2200
EPS5
EPS5
EPR48-3G
3
4
2700
3600
EPS5
EPS5
EPR48-3G
3
4
5
5
63