Connections Of Current Terminals - Siemens SIPROTEC 5 Compact Hardware Description

Hide thumbs Also See for SIPROTEC 5 Compact:
Table of Contents

Advertisement

Working on the Device
5.3 Installing Current and Voltage Terminals
Terminal
4 protection-class current
transformers
3 protection-class current
transformers and 1 instru-
ment transformer
5.3.2

Connections of Current Terminals

Fasteners
The fasteners for the transformer connection are part of the current terminal (housing side). They are made of
a stress-crack and corrosion-free alloy. The head shape of the clamping screw allows the use of a DIN 5.5 x 1.0
screwdriver or a PZ2 screwdriver. Siemens recommends a PZ2 screwdriver.
Connection Elements and Conductor Cross-Sections
The following connection types are possible:
Stranded-wire conductor with ring-type lug
Stranded-wire conductor with bootlace ferrule
Solid conductor
Siemens recommends the use of ring-type lugs with the dimensions shown in the following figure. Use copper
cables only.
[dwringka-030211-01.tif, 1, en_US]
Figure 5-9
D (for bolt)
W
L
In order to maintain the insulation route, you must use insulated cable lugs or you must insulate the crimping
zone (for example, by using heat-shrink tube insulation)
Siemens recommends ring-type lugs of the PIDG series made by Tyco Electronics.
Use copper conductors only, at least certified for a temperature of +105 °C. Use prepared solid conductors
intended for single or multi-wiring connection, maximum 2 wires per pole, and for usage of ferrules, crimped-
on pressure wire connectors (ring-type and pin-type).
2 terminal lugs can be installed for each connection.
48
DIGSI
Current 4x protection
Current 3x protection,
1x measurement
Ring-Type Lug
Terminal Labeling
C73334A 1D285 1
C73334A 1D286 1
5.0 mm (0.2 in)
9.5 mm (0.37 in)
7.1 mm to 7.7 mm (0.28 in to 0.3 in)
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5300-C002-3, Edition 12.2021
Ordering No. (Short Desig-
nation)
7XX8410-0CF00
7XX8410-0CG00

Advertisement