6.4
Relay Outputs
Relay Outputs
Fast relay (type F)
Making capacity
Breaking capacity
AC and DC contact voltage
Permissible current per contact
(continuous)
Permissible current per contact
(switching on and holding)
Short-time current across closed
contact
Total permissible current for
contacts connected to common
potential
Switching time OOT
Rated data of the output contacts
in accordance with UL certification
Interference suppression capacitors
across the contacts
Monitoring
3
OOT (Output Operating Time): Additional delay of the output medium used, for example, 1 ms with electronic relays
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5300-C002-3, Edition 12.2021
Max. 1000 W (L/R = 40 ms)
Max. 3600 VA (power factor ≥ 0.35, 50 Hz to 60 Hz)
Max. 30 W (L/R = 40 ms)
Max. 360 VA (power factor ≥ 0.35, 50 Hz to 60 Hz)
250 V
5 A
30 A for 1 s (make contact)
250 A for 30 ms
5 A
3
Make time: typical: 4 ms; maximum: 5 ms
Break time: typical: 2 ms; maximum: 5 ms
DC 24 V, 5 A, General Purpose
DC 48 V, 0.8 A, General Purpose
DC 240 V, 0.1 A, General Purpose
AC 120 V, 5 A, General Purpose
AC 250 V, 5 A, General Purpose
AC 250 V, 0.5 hp
B300
R300
4.7 nF, ± 20 %, AC 250 V
2-channel activation
Technical Data
6.4 Relay Outputs
57