7. Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compres-
sor OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In micom dehumidify mode, control of fan speed is as following.
Intake Air temp.
Setting temp. +1.0˚C
(Compressor ON)
Setting temp.
Setting temp. -0.5˚C
(Compressor OFF)
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
8. Protection of the evaporator pipe from frosting
mperature of the indoor coil is below 0°C after 7 minutes from starting the compressor, the
If the te
compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor and the
temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoperated.
Indoor fa
n operates at low speed (comp. OFF) or at selected speed (comp. ON)
9. Test Operation
• When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan
regardless of room temperature and resets in 18 min.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
10. Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance should be on the automatically operates in the mode
on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)
• If no input by the remote controller or no switching of the slide switch within 7 hr after the appliance operates
by the Auto Restarting operation, the appliance is forced to stop at the moment of 7-hr elapse.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cooling
2min.58sec.
10min.
7min.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Selected
Low Fan
Fan
10min.
Within 7min. Cooling
ON
OFF
ON
OFF
Selected
- 16 -
2min.58sec.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Low Fan
Fan