LG LV-C362FLA0 Svc Manual page 15

Ceiling & floor type air conditioner
Table of Contents

Advertisement

• Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button,
louver moves as following cycle.
MODE0
MODE1
6. Natural wind by CHAOS logic
Intake Air temp.
Cooling on temp.
(Setting temp.+0.5)
Setting temp.
Cooling off temp.
(Setting temp.-0.5)
INDOOR FAN
OUTDOOR FAN/COMP.
: Setting fan speed
GRAPH of Natural wind by the CHAOS logis (During Cooling operation)
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
MODE2
MODE3
MODE4
End
MODE5
MODE6
Setting CHAOS Natural wind
: CHAOS Natural wind
Start
For more fresh feeling than other fan speed mode, press
the indoor fan Speed Selector and set to CHAOS mode.
In this mode, the wind blows like natural breeze by auto-
matically changing fan speed according to the CHAOS
logic.
: LOW
: COMP ON
- 15 -
MODE9
(CLOSED)
: COMP OFF
LGE Internal Use Only