LG LV-C362FLA0 Svc Manual page 14

Ceiling & floor type air conditioner
Table of Contents

Advertisement

4. Cooling Mode with Sleep Mode Auto Operation
• When selecting the Cooling(
is as following.
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
INDOOR FAN
COMPRESSOR
5. Auto Operation
Operation Condition
When Auto Operation
initial start
When pressing room temp-
erature setting button
during Auto Operation
Intake-Air temp
Setting Temp. +0.5°C
(Compressor OFF)
Setting Temp.-0.5°C
(Compressor ON)
Indoor Fan
Compressor
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
) combined with the Sleep Mode Auto Operation(
30 minutes
More than
3 minutes
Low
Low
ON
OFF
Intake-air Temperature
Over 26°C
Over 24°C~below 26°C
Over 22°C~below 24°C
Over 20°C~below 22°C intake air temperture
below 20°C
Over 20°C~below 30°C
below 20°C
over 30°C
ON
1°C
More than
3 minutes
Low
Low
ON
OFF
Setting temperature
Fan speed
25°C
Intake air -1°C
Intake air -0.5°C
Controlled
20°C
by Fuzzy logic
Fuzzy control
20°C
30°C
Fuzzy Speed
OFF
- 14 -
), the operation diagram
30 minutes
Low
ON
Air Direction Control
In this mode, when
pressing the verti-
cal air diretion con-
trol.
Button, louvers
moves to 1/f
rhythm (refer to
page 15)
ON
OFF
LGE Internal Use Only