WARNING
The
limitation
adjustable between 1 and 5.5 A. The
genset breaker must be open during the
short circuit. If the genset is restarted in
short circuit, there is a excitation build
up during 10s again at the maximum
value.
Operation between 3 and 6 In when
short-circuited:
The excitation current ceiling during a
short-circuit equals 2.9 times the fixed
threshold when setting the permitted
excitation ceiling in continuous operation.
When the threshold is exceeded for a period
= 10 s the current is reduced to a value
between 0.5 and 0.7 A (shutdown).
In all operating conditions the maximum
excitation current must be limited to
9 A ± 0.5 A.
I exc(A)
2.9x I
9.5
threshold
(max. 9.5 A)
P3
I
threshold
(1...5.5A)
Shutdown
0.5 ~ 0.7
Red led
Green led
CALL US TODAY
1-888-POWER-58
Installation and maintenance
threshold
must
(Maximum current I exc)
Activation of
90 s tempo.
Decrease of
90 s tempo.
REQUEST A QUOTE
generators@genpowerusa.com
R450
A.V.R.
Overrun indications:
One green LED:
- Lights up when the excitation current is
be
below the continuous operation threshold
It signals the AVR normal operation.
- Turns off when the excitation current ceiling
used to obtain short-circuit operation is
reached and when the excitation current is
reduced to the shutdown value.
- Flashes when the over excitation counter
is decrementing.
NB: After an obvious short-circuit, the
voltage is limited to 70% of the rated voltage.
This avoids overvoltages on machines
whose no-load excitation current is below
the "lower current" threshold (only in AREP).
Activation of
Activation of
10 s tempo.
90 s tempo.
4531 en -
2016.06 / h
Diagram 1
10s tempo. elapsed :
shutdown apllication
www.genpowerusa.com/leroy-somer-avr/
t(s)
9