( 2 ) Troubleshooting 2
An error code displays on the remote controller.
The LED on the Lossnay circuit board is blinking or lit up.
An error code displayed on the remote controller ( PZ-60DR-E ) or the M-NET controller, and blinking or illumina-
tion of LED1 ( green ) or LED2 ( red ) on the circuit board shows the type of an error. The LED blink interval is
0.25 seconds for both on and off. The display duration is approximately 5 seconds.
Checklist of error codes displayed on the PZ-60DR-E ( when not using M-NET ) , and LED displays ( Table 2-1 )
Error code LED1
LED2
( green )
( red )
LC 6608
RC 6608
SRC 6608
RC 6201,6202
SRC 6201,6202
LC 0900
SLC 0900
LC 3126
8
SLC 3126
blinks
0.25S 0.25S 0.25S
ON
OFF
Error display example: ( Two blinks )
Error
Lossnay
When multiple Lossnay units are
communi-
used, the Main/Sub setting has not
cation error
been made for the second unit and
following units.
Multiple transmission cables are
wired with multi core cables.
Transmission cable and power
cable are too close.
Transmission cable is not securely
connected.
The length of the transmission ca-
ble wiring is longer than specified
( longer than 547 yd. (500 m) ) .
Communication
Multiple transmission cables are
error between
wired with multi core cables.
remote con-
trollers ( when
Transmission cable and power
two remote
supply cable are too close.
controllers are
Transmission cable is not securely
connected )
connected.
The length of the transmission ca-
ble wiring is longer than specified
( longer than 547 yd. (500 m) ) .
Remote
The remote controller has broken
controller
down.
error
Lossnay
Trial operation switch on the
Lossnay circuit board ( SW2-1 ) is
trial opera-
tion
set to ON.
External
When the TM3 6, 7 output set-
device error
ting switch ( SW5-6 ) is ON, the
following conditions are applied.
• OA temperature is still 14°F
(-10°C) or lower, 60 minutes after
the output started
• OA temperature is 59°F (15°C) or
higher within 15 minutes after the
output started
• OA temperature is 158°F (70°C)
or higher
5S
Cause
─ 44 ─
Action
Turn off the main power supply and
set the Main/Sub selection switch
( SW1 ) ( first unit to " Main " , second
and following units to " Sub ") .
Use suitable cables to wire the
transmission cables so that they
are separated from one another.
Wire the transmission cable at least 2 in. (5
cm) away from the power supply cable.
Check the transmission cable con-
nection.
Check the length of the transmis-
sion cable wiring.
Use suitable cables to wire the
transmission cables so that they
are separated from one another.
Wire the transmission cable at least 2 in. (5
cm) away from the power supply cable.
Check the transmission cable con-
nection.
Check the length of the transmis-
sion cable wiring.
Replace the remote controller.
Check the trial operation switch.
( Refer to page 30 )
When external devices are con-
nected, check the external de-
vices.
When external devices are not
connected, check the TM3 6,
7 output setting switch ( SW5-6 ) .
( Refer to page 30 )