Mitsubishi Electric LGH-F300RX5-E1 Handbook page 42

Hide thumbs Also See for LGH-F300RX5-E1:
Table of Contents

Advertisement

No.
Error
3
Interlock operation
with external device
does not occur.
Note: When two remote controllers are used, the combination of the PZ-60DR-E and other remote controller cannot
be used.
System checklist when using the M-NET ( Table 1-2-2 )
No.
Error
1
Lossnay does not in-
terlock with City Multi
indoor unit. ( Lossnay
cannot be operated by
the ventilation button on
the ME remote control-
ler, MA remote controller
or MELANS. )
2
Cannot operate the
Lossnay using MELANS
or the Lossnay remote
controller.
3 A Lossnay unit should
operate independently
by MELANS or the
Lossnay remote control-
ler, but it interlocks with
different City Multi units.
Cause
 The interlock mode is set to " ON Interlocked "
or " OFF Interlocked " with the remote controller
( PZ-60DR-E ) .
 When PZ-60DR-E is not used, the delay setting
switch ( SW5-1 ) on the Lossnay circuit board is
set to ON. ( During the delay operation, LED1
( green ) on the Lossnay circuit board will be lit. )
 When PZ-60DR-E is not used, the interlock
mode setting switches ( SW5-7, SW5-8 ) on the
Lossnay circuit board are set to " ON Interlocked "
or " OFF Interlocked " .
 When multiple Lossnay units are used, the
external control input signal is connected to a
unit set to " Sub " .
 Remote/local switching ( CN32 ) is used.
 Lossnay is not set for interlock operation,
or is set for interlock operation at the wrong
address.
 The length of the M-NET transmission cable
wiring from the outdoor unit or the system's
overall wiring length is longer than speci-
fied. ( Longer than 219 yd. (200 m) from the
outdoor unit, longer than 547 yd. (500 m)
between ends. )
 The address that has been set for the
group in MELANS and the address for the
Lossnay are different.
 The length of the M-NET transmission ca-
ble wiring from the power supply unit or the
system's overall wiring length is longer than
specified. ( Longer than 219 yd. (200 m)
from the power supply unit, longer than 547
yd. (500 m) between ends. )
 It has been set for interlock operation with
the City Multi units.
Cause
─ 42 ─
Action
 Check the Interlock mode setting
with the remote controller ( PZ-
60DR-E ) . ( Refer to page 24 )
 Check the setting of the delay
setting switch ( SW5-1 ) on the
Lossnay circuit board. ( Refer to
page 30 )
 Check the setting of the interlock
mode setting switch ( SW5-7,
SW5-8 ) on the Lossnay circuit
board. ( Refer to page 30 )
 Connect the external control
input signal to the Lossnay unit
set to " Main. "
 When interlocked with external
devices, remote/local switching
( CN32 ) cannot be used.
Action
 Check the Lossnay address, and
set for an address corresponding
to interlock operation.
 Check the length of the transmis-
sion cable wiring.
( See the technical manual for
details about the regulations. )
 Check the registered address in
MELANS.
 Check the length of the transmis-
sion cable wiring.
( See the technical manual for
details about the regulations. )
 Cancel the interlock operation
setting.