Mitsubishi Electric LGH-F300RX5-E1 Handbook page 31

Hide thumbs Also See for LGH-F300RX5-E1:
Table of Contents

Advertisement

Type
Name
SW5
9
Cold region operation at out-
door air temperature of 5°F
(-15°C) or lower
Note 3
10
Type setting
Note 1
SW6
1
Type setting Note 3
2
Type setting Note 3
3
Type setting Note 3
4
Type setting Note 3
Note 1: Set LGH-F300 to F600 types to the OFF setting, and LGH-F1200 type to the ON setting. The system
will not operate properly when the setting is changed.
Note 2: When the aforementioned switches (SW2 and SW5) are at the factory setting, LGH-F300 to F600
types will all be at the OFF setting, and LGH-F1200 type will all be set to OFF except for SW5-10.
When replacing the circuit board, set the new board to the same setting as that of the board prior to
replacement.
Note 3: Set the switch before turning on the power. To change the setting after power supplied, reset the power.
• Main/Sub selection switch
In systems of only one Lossnay unit, be sure to set it to "Main".
In systems with multiple Lossnay units, be sure that one unit is set to "Main", and that all the others are
set to "Sub".
When interlocked with an external device, be sure to connect the external device to the Lossnay that is
set to "Main".
When using PZ-60DR-E and mixing the LGH-F300 to F600 types together with the LGH-F1200 type in a
group, set the LGH-F300 to F600 types as "Main". ( When the LGH-F1200 type is set to "Main", Extra Low
operation is not possible. )
( 11 ) Function selection with PZ-60DR-E
When PZ-60DR-E is used, function selection can be made from the remote controller.
Functions can be switched from PZ-60DR-E even after the function selection switch has been set on the
Lossnay circuit board.
( Settings from PZ-60DR-E will have priority over function selection switch settings of the Lossnay circuit
board.)
When two remote controllers are used, "24HR VENTILATION", "LOSSNAY FUNCTION", and "INTERLOCK
SETTING" can be set only on the "Main" remote controller.
The "Main" and "Sub" remote controller will be determined automatically by communication when the main unit
power is turned on. The side on which "24HR VENTILATION", "LOSSNAY FUNCTION", and "INTERLOCK
SETTING" are displayed is the "Main" remote controller.
* For information about operation of PZ-60DR-E, refer to the Lossnay remote controller PZ-60DR-E Installation
Manual and the Operating Instructions.
ON : When the indoor dew point is less than 41°F (6°C)
(Indoor condition: 68°F (20°C) 40%RH)
OFF: When the indoor dew point is less than 53.6°F (12°C)
(Indoor condition: 75.2°F (24°C) 50%RH) ( Factory setting )
LGH-F300 to F600 types : Fixed at OFF
LGH-F1200 type
Fixed at ON
Fixed at ON
Fixed at OFF
Fixed at OFF
─ 31 ─
Specification
: Fixed at ON