6.2.2 To mount the unit

BEV2N-A
CO₂ Conveni-Pack: BEV2 unit
4P677928-1 – 2021.10
a Suspension bolt pitch
Hanger bracket. Make sure to support the connection piping around the unit
using hanger brackets installed within 1  meter of the side of the unit. Avoid
putting excessive weight on the hanger bracket; otherwise the unit may fall and
cause injuries.
≤1 m
a Unit
b Anchor
c Long nut or turnbuckle
d Suspension bolt
e Hanger bracket
Changing the installation position of the control box
Prerequisite: The position of the control box can be changed if necessary.
2
1
a
b
b e
f
f
a Control box lid
b Control box
c Top panel
d Coil cover
e Wire clip
f Tie wrap
1 Remove the control box lid (2 screws).
2 Remove the control box (2 screws).
3 Remove the top panel (4 screws).
4 Remove the coil cover (1 screw).
5 Change the pull out direction of the wire (motorised valve coil) between the
unit body and the control box.
b
c
d
a
≤1 m
c
3, 8
180°
6
4, 7
d
5
5
e
b
e
f
6
Unit installation
|
e
10
9
b
a
f
e
Installer reference guide
19