6
|

Unit installation

6 Unit installation
In this chapter

6.1 Preparing the installation site

6.1.1 Installation site requirements of the unit

Installer reference guide
16
WARNING
Installation shall be done by an installer, the choice of materials and installation shall
comply with the applicable legislation. In Europe, EN378 is the applicable standard.
WARNING
Make sure to install all necessary countermeasures in case of refrigerant leakage
according to standard EN378 (see
for CO₂
refrigerant" [
Make sure to install a CO
refrigerant piping, air conditioning units, showcases or blower coils, and enable
the function for refrigerant leak detection (see the installation manual of the
indoor units).
6.1
Preparing the installation site ................................................................................................................................................
6.1.1
Installation site requirements of the unit..............................................................................................................
6.1.2
Additional installation site requirements for CO₂ refrigerant...............................................................................
6.2
Mounting the unit...................................................................................................................................................................
6.2.1
Guidelines when installing the unit .......................................................................................................................
6.2.2
To mount the unit ..................................................................................................................................................
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
INFORMATION
Also read the general installation site requirements. See the
4
precautions" [
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.
"6.1.2 Additional installation site requirements
4
 18]).
leak detector (field supply) in every room with
2
 4]" chapter.
16
16
18
18
18
19
""2  General safety
BEV2N-A
CO₂ Conveni-Pack: BEV2 unit
4P677928-1 – 2021.10