Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

Controls
Table 18: RCU database controls
C_PID
Name/target/control type/controls
Clear protocol counters
Target: Remote control unit (RCU)
0
Control type: Unary control
Controls: Clear counters
Trip/close ganged
Target: Line (Fusesaver all phases)
1
Control type: Binary control
Controls: Trip/close
Trip/close any
Target: Line (Fusesaver all phases)
2
Control type: Binary control
Controls: Trip/close
Phase A trip/close
Target: Fusesaver phase A
3
Control type: Binary control
Controls: Trip/close
Phase B trip/close
Target: Fusesaver phase B
4
Control type: Binary control
Controls: Trip/close
Phase C trip/close
Target: Fusesaver phase C
5
Control type: Binary control
Controls: Trip/close
RCU dummy control
Target: RCU
6
Control type: Binary control
Controls: Trip/close
Fusesaver dummy control
Target: Fusesaver all phases
7
Control type: Binary control
Controls: Trip/close
34
RCU database controls
This control will reset all protocol counters in the RCU to 0.
Trip command will issue a trip command to all the Fusesavers (all phases) on the line but
only if communications are normal to each and every Fusesaver. If communications have
failed to any Fusesaver, no trip will be sent to any Fusesaver.
Close command will issue to a close command to all the Fusesaver (all phases) on the line
but only if communications are normal to each and every Fusesaver. If communications
have failed to any Fusesaver, no trip will be sent to any Fusesaver.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
Trip command will issue a trip command to any Fusesavers which are configured and to
which communications are normal.
Close command will issue to a close command to any Fusesavers which are configured
and to which communications are normal.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
Trip command will issue a trip command to the A-phase Fusesaver if configured.
Close command will issue to a close command to the A-phase Fusesaver if configured.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
Trip command will issue a trip command to the B-phase Fusesaver if configured.
Close command will issue to a close command to the B-phase Fusesaver if configured.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
Trip command will issue a trip command to the C-phase Fusesaver if configured.
Close command will issue to a close command to the C-phase Fusesaver if configured.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
This is a dummy control point, which can be used for test purposes. It controls the RCU
dummy input point (D_PID 57).
Trip command will clear the dummy input point on the RCU.
Close command will set the dummy input point on the RCU.
This is a dummy control point, which can be used for test purposes. It controls the
Fusesaver dummy input points (D_PID 58, 59, 60).
Trip command will clear the dummy input points on all Fusesavers that are in
communication.
Close command will set the dummy input points on all Fusesavers that are in
communication.
Controls will only be accepted if D_PID 101 (remote control enabled) is set. If not, then
the control will be rejected with the relevant control response control.
Description