Siemens 3AD8 Instruction Manual page 25

Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

D_PID
Phase
Fusesaver - In force protection mode -
fast single
Source: Fusesaver
77
A
78
B
States: ‒/protection mode in force fast
79
C
single
Event time tag: Remote control unit (RCU)
time
Fusesaver - In force protection mode - off
80
A
Source: Fusesaver
81
B
States: ‒/protection mode in force off
82
C
Event time tag: RCU time
Fusesaver - Tribe running
Source: Fusesaver
States: Tribe not running/tribe running
83
A
84
B
Event time tag: Events not generated.
85
C
Note: These points are essentially internal
Fusesaver operation and do not normally
need to be used by SCADA system for
operational purpose.
Fusesaver - Charged capacitors
Source: Fusesaver
States: Capacitors not charged/capacitors
86
A
charged
87
B
Event time tag: Events not generated.
88
C
Note: These points are essentially internal
Fusesaver operation and do not normally
need to be used by SCADA system for
operational purpose.
Fusesaver - Trip pending
89
A
Source: Fusesaver
90
B
States: Trip not pending/trip pending
91
C
Event time tag: RCU time
Fusesaver - Close pending
92
A
Source: Fusesaver
93
B
States: Close not pending/close pending
94
C
Event time tag: RCU time
Fusesaver - Remote protection mode -
normal single
95
A
Source: Fusesaver
96
B
States: ‒/remote protection mode normal
97
C
single
Event time tag: RCU time
RCU database digital points list
Name/states/source
Status/events/restart/qualifiers
State: Set when Fusesaver in force protection mode is set to fast single. Cleared
when Fusesaver in force protection mode is set to normal, normal single, fast or
off. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver in force protection mode is set to off. Cleared when
Fusesaver in force protection mode is set to normal, normal single, fast or fast
single. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver tribe is running. Cleared when Fusesaver tribe is not
running. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when the Fusesaver capacitors are charged. Cleared when Fusesaver
capacitors are not charged. This status data comes from the Fusesaver live-data
stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when the Fusesaver has a trip control pending. Cleared when the
Fusesaver has no trip control pending. This status data comes from the
Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when the Fusesaver has a close control pending. Cleared when the
Fusesaver has no close control pending. This status data comes from the
Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver remote protection mode is set to normal single.
Cleared when Fusesaver remote protection mode is set to normal, fast, fast
single or off. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
25