10.2.4 Connect the Cable to the Indoor Unit
1
Install the indoor unit on the installing holder that mounted on the wall.
2
Remove front grille by loosening the screw.
3
Remove metal cover without damaging aluminium foil.
4
Cable connection to the power supply through Isolating Devices
(Disconnecting means).
Connect the approved PVC sheathed or polychloroprene sheathed
o
power supply cord 3 x 1.5 mm
type designation IS 694 or 60245 IEC 57 or heavier cord to the terminal
board, and connect the other end of the cable to Isolating Devices
(Disconnecting means).
Do not use joint power supply cord. Replace the wire if the existing wire
o
(from concealed wiring, or otherwise) is too short.
In unavoidable case, joining of power supply cord between isolating
o
devices and terminal board of air conditioner shall be done by using
approved socket and plug rated 15/16A (1.5HP) or 16A (2.0HP) or 20A
(2.5HP). Wiring work to both socket and plug must follow to national
wiring standard.
5
Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
6
Connection cable between indoor unit and outdoor unit shall be approved type PVC sheathed or
polychloroprene sheathed 3 x 1.0 mm
cord. Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
7
Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.
8
Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor
unit according to the diagram below.
2
(1.5HP) or 3 x 2.5 mm
2
(1.5HP) or 3 x 1.5 mm
23
2
(2.0~2.5HP),
2
(2.0~2.5HP) or 3 x 2.5 mm
2
(2.5HP) flexible