This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death.
Indoor Unit
CS-UC12QKD
CS-UC18QKD
CS-UC24QKD
WARNING
Order No. APIN1404001CE
Air Conditioner
Outdoor Unit
CU-UC12QKD
CU-UC18QKD
CU-UC24QKD
(Manufactured in India)
Destination
Ivory Coast
© Panasonic Corporation 2014
Senegal

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CS-UC12QKD

  • Page 1 Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death. © Panasonic Corporation 2014...
  • Page 2: Table Of Contents

    2. Specifications .............5 14.1 Refrigeration Cycle System ......38 3. Location of Controls and Components....7 15. Disassembly and Assembly Instructions ..40 Indoor Unit .............7 15.1 CS-UC12QKD..........40 Outdoor Unit...........7 15.2 CS-UC18QKD CS-UC24QKD ....45 Remote Control..........7 16. Technical Data ..........50 4.
  • Page 3: Safety Precautions

    1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. The caution items stated here must be followed because these important contents are related to safety.
  • Page 4 WARNING 19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
  • Page 5: Specifications

    2. Specifications Indoor CS-UC12QKD CS-UC18QKD CS-UC24QKD Model Outdoor CU-UC12QKD CU-UC18QKD CU-UC24QKD Performance Test Condition India Standard Phase, Hz Single, 50 Power Supply 3.34 3.36 5.42 5.45 6.48 6.50 Capacity BTU/h 11400 11500 18500 18600 22100 22200 kcal/h 2870 2890 4660...
  • Page 6 Indoor CS-UC12QKD CS-UC18QKD CS-UC24QKD Model Outdoor CU-UC12QKD CU-UC18QKD CU-UC24QKD 290 (11-7/16) / 290 (11-7/16) / 290 (11-7/16) / Height (I/D / O/D) mm (inch) 619 (24-3/8) 619 (24-3/8) 619 (24-3/8) 870 (34-9/32) / 1070 (42-5/32) / 1070 (42-5/32) / Dimension...
  • Page 7: Location Of Controls And Components

    3. Location of Controls and Components Indoor Unit Outdoor Unit Remote Control...
  • Page 8: Dimensions

    4. Dimensions Indoor Unit & Remote Control 4.1.1 CS-UC12QKD...
  • Page 9 4.1.2 CS-UC18QKD CS-UC24QKD...
  • Page 10: Outdoor Unit

    Outdoor Unit...
  • Page 11: Refrigeration Cycle Diagram

    5. Refrigeration Cycle Diagram...
  • Page 12: Block Diagram

    6. Block Diagram...
  • Page 13: Wiring Connection Diagram

    7. Wiring Connection Diagram CS-UC12QKD CU-UC12QKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-UC12QKD MODEL CU-UC12QKD CONNECTION CWA951802 CONNECTION 2PS192D3BA06 BLUE-YELLOW 357.6 Ω C - R 4.673 Ω YELLOW-RED 252.3 Ω C - S 4.895 Ω...
  • Page 14: Cs-Uc18Qkd Cu-Uc18Qkd

    CS-UC18QKD CU-UC18QKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-UC18QKD MODEL CU-UC18QKD CONNECTION CWA951802 CONNECTION 2KS324D5CB06 BLUE-YELLOW 357.6 Ω C – R 1.716 Ω YELLOW-RED 252.3 Ω C - S 2.704 Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
  • Page 15: Cs-Uc24Qkd Cu-Uc24Qkd

    CS-UC24QKD CU-UC24QKD Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-UC24QKD MODEL CU-UC24QKD CONNECTION CWA921512 CONNECTION 2V40S225AUC BLUE-YELLOW 129.3 Ω C - R 1.367 Ω YELLOW-RED 78.3 Ω C - S 1.981 Ω Note: Resistance at 20°C of ambient temperature. Note: Resistance at 20°C of ambient temperature.
  • Page 16: Electronic Circuit Diagram

    8. Electronic Circuit Diagram CS-UC12QKD...
  • Page 17: Cs-Uc18Qkd Cs-Uc24Qkd

    CS-UC18QKD CS-UC24QKD...
  • Page 18: Printed Circuit Board

    9. Printed Circuit Board Indoor Unit 9.1.1 Main Printed Circuit Board...
  • Page 19 9.1.2 Indicator and Receiver Printed Circuit Board...
  • Page 20: Installation Instruction

    10. Installation Instruction 10.1.3 Indoor/Outdoor Unit Installation 10.1 Select the Best Location Diagram 10.1.1 Indoor Unit Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam near the unit.
  • Page 21: Indoor Unit

    10.2 Indoor Unit 10.2.1 How to Fix Installation Plate 10.2.2 To Drill a Hole in the Wall and Install The mounting wall shall be strong and solid enough to a Sleeve of Piping prevent it from the vibration. Insert the piping sleeve to the hole. Fix the bushing to the sleeve.
  • Page 22 1. For the Right and Right Bottom Piping 2. For the Embedded Piping (This can be used for left rear piping and bottom piping also.)
  • Page 23 10.2.4 Connect the Cable to the Indoor Unit Install the indoor unit on the installing holder that mounted on the wall. Remove front grille by loosening the screw. Remove metal cover without damaging aluminium foil. Cable connection to the power supply through Isolating Devices (Disconnecting means).
  • Page 24 Secure the power supply cord and connection cable onto the control board with the holder. 10 Fix back metal cover to original position without damaging aluminium foil. Ensure metal cover is fitted at both end. 11 Install front grille and tighten front grille to chassis with screw. WARNING This equipment must be properly earthed.
  • Page 25 10.2.5 Wire Stripping and Connecting Requirement...
  • Page 26: Outdoor Unit

    10.3 Outdoor Unit 10.3.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
  • Page 27 FOR ENVIRONMENTAL PROTECTION, MANUFACTURER STRONGLY RECOMMENDS TO USE EVACUATION METHOD. 10.3.3 Evacuation of the Equipment Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Be sure to connect the end of the charging hose with the push pin to the service port. Connect the center hose of the charging set to a vacuum pump.
  • Page 28 10.3.4 Air Purging of the Piping and Indoor The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compressor. Remove the caps from the 2-way and 3-way valves. Remove the service-port cap from the 3-way valves. To open the valve, turn the valve stem of 2-way valve counter-clockwise approx.
  • Page 29 10.3.6 Piping Insulation Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above.
  • Page 30: Operation And Control

    11. Operation and Control 11.1 Cooling Operation Cooling operation can be set using remote control. This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C.
  • Page 31: Indoor Fan Speed Control

    11.2 Indoor Fan Speed Control Indoor Fan Speed can be set using remote control. 11.2.1 Fan Speed Rotation Chart Speed Fan Speed (rpm) UC12QKD UC18QKD UC24QKD 1180 1320 1470 1000 1190 1310 H Lo 1130 1210 C Lo 1060 1150 S Lo 11.2.2 Automatic Fan Speed Control When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the...
  • Page 32: Outdoor Fan Speed Control

    11.2.3 Manual Fan Speed Control Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. There are 3 types of fan speed settings: Lo, Me, Hi. 11.2.4 Indoor Fan Motor RPM Abnormal Control Immediate after the fan motor is started, rpm abnormal control is performed once every second.
  • Page 33: Horizontal Airflow Direction Control

    11.5 Horizontal Airflow Direction Control The horizontal airflow direction louvers can be adjusted manually by hand. 11.6 Timer Control 11.6.1 To Set the Timer To turn ON the unit at a preset time, set the timer while the unit is OFF (the operation will start 15 minutes early before the preset time).
  • Page 34 Fan Speed Control Follow setting fan speed Note: (1) Sleep mode maximum running hour is 8. After 8 hours, unit off automatically. (2) When unit resume from power failure, it will resume operation at previous setting, except sleep mode.
  • Page 35: Protection Control

    12. Protection Control 12.1 Restart Control (Time Delay Safety Control) When the thermo-off temperature (temperature which compressor stops to operate) is reached during: - Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation. If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation stop, although the unit is turn on again within the period.
  • Page 36: Compressor Reverse Rotation Protection Control

    12.6 Compressor Reverse Rotation Protection Control If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
  • Page 37: Servicing Mode

    13. Servicing Mode 13.1 Auto OFF/ON Button OPERATION MODE The operation will be activated immediately once the AUTO OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunctioned. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
  • Page 38: Troubleshooting Guide

    14. Troubleshooting Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right.
  • Page 39 14.1.1 Relationship between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Condition of the air conditioner Low Pressure High Pressure Electric current during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression...
  • Page 40: Disassembly And Assembly Instructions

    High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 15.1 CS-UC12QKD 15.1.1 Small Air Filter, Indoor Electronic Controllers and Control Board Removal...
  • Page 43 15.1.2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
  • Page 45: Cs-Uc18Qkd Cs-Uc24Qkd

    15.2 CS-UC18QKD CS-UC24QKD 15.2.1 Small Air Filter, Indoor Electronic Controllers and Control Board Removal Procedures...
  • Page 48 15.2.2 To Remove Cross Flow Fan and Indoor Fan Motor...
  • Page 50: Technical Data

    16. Technical Data 16.1 Thermostat Characteristics Cooling...
  • Page 51: Operation Characteristics

    16.2 Operation Characteristics 16.2.1 CS-UC12QKD CU-UC12QKD Cooling Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Piping length: 5.0 m 16.600 16.400 16.200 16.000 15.800 15.600 15.400 15.200 15.000 14.800 14.600 Outdoor Air Temperature (°C) 3.600 3.500...
  • Page 52 Piping Length Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Outdoor temperature: 35/24°C Piping length: 5.0 m 15.800 15.700 15.600 15.500 15.400 15.300 15.200 15.100 Piping Length (m) 3.400 3.350 3.300 3.250 3.200 3.150 Piping Length (m) 4.950 4.900 4.850...
  • Page 53 16.2.2 CS-UC18QKD CU-UC18QKD Cooling Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Piping length: 5.0 m 15.800 15.600 15.400 15.200 15.000 14.800 14.600 14.400 14.200 14.000 Outdoor Air Temperature (°C) 6.000 5.800 5.600 5.400 5.200 5.000 4.800 4.600...
  • Page 54 Piping Length Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Outdoor temperature: 35/24°C Piping length: 5.0 m 15.100 15.000 14.900 14.800 14.700 14.600 14.500 14.400 Piping Length (m) 5.500 5.450 5.400 5.350 5.300 5.250 5.200 5.150 Piping Length (m) 8.300...
  • Page 55 16.2.3 CS-UC24QKD CU-UC24QKD Cooling Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Piping length: 5.0 m 14.800 14.600 14.400 14.200 14.000 13.800 13.600 13.400 13.200 13.000 Outdoor Air Temperature (°C) 7.000 6.800 6.600 6.400 6.200 6.000 5.800 5.600...
  • Page 56 Piping Length Characteristic [Condition] Room temperature: 27°C (DBT), 19°C (WBT) Operation condition: High fan speed Outdoor temperature: 35/24°C Piping length: 5.0 m 14.000 13.900 13.800 13.700 13.600 13.500 13.400 Piping Length (m) 6.600 6.500 6.400 6.300 6.200 6.100 Piping Length (m) 9.900 9.800 9.700...
  • Page 57: Exploded View And Replacement Parts List

    17. Exploded View and Replacement Parts List 17.1 Indoor Unit 17.1.1 CS-UC12QKD Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 58 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-UC12QKD REMARK CHASSIS-COMPLETE CWD50C1769-AN# FAN MOTOR CWL6CBYYYL0037 CROSS-FLOW FAN-COMPLETE CWH02C1147 FIN & TUBE EVAPORATOR-COMPLETE CWB30C4702-AN UNION NUT CWT251026 UNION NUT CWT251062 HOLDER-SENSOR CWH321110 PARTICULAR PIECE CWD933740 TERMINAL BOARD-COMPLETE CWA28C2605 ELECTRONIC CONTROLLER - MAIN...
  • Page 59 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-UC12QKD REMARK CWH52061 SELF TAPPING SCREW CWXTT4+10CFJ Note: All parts are supplied from APIN, India (Vendor Code: 00026071). “O” marked parts are recommended to be kept in stock.
  • Page 60 17.1.2 CS-UC18QKD CS-UC24QKD Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 61 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-UC18QKD CS-UC24QKD REMARK CHASSIS-COMPLETE CWD50C1778-AN ← FAN MOTOR CWL6CBYYYL0037 CWL6CBYYYL0039 CROSS-FLOW FAN-COMPLETE CWH02C1077 ← FIN & TUBE EVAPORATOR-COMPLETE CWB30C4704-AN CWB30C4536-AN# UNION NUT CWT251026 ← UNION NUT CWT251062 CWT251036 PARTICULAR PIECE CWD933753 ← TERMINAL BOARD-COMPLETE CWA28C2604 CWA28C2606...
  • Page 62 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-UC18QKD CS-UC24QKD REMARK C.C. CASE CWG569673 ← SELF TAPPING SCREW CWXTT4+10CFJ ← Note: All parts are supplied from APIN, India (Vendor Code: 00026071). “O” marked parts are recommended to be kept in stock.
  • Page 63: Outdoor Unit

    17.2 Outdoor Unit Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 64 REF. SAFETY PART NAME & DESCRIPTION QTY. CU-UC12QKD CU-UC18QKD CU-UC24QKD REMARK BASE PAN ASS'Y CWD52K1356-AN CWD52K1332-AN ← FAN MOTOR BRACKET CWD541219-AN ← ← FAN MOTOR CWA951802 ← CWA921512 SCREW CWH55406J ← ← FAN ASSY CWH03K1087 ← ← CWH56053J ← ← COMPRESSOR 2PS192D3BA06 2KS324D5CB06...

This manual is also suitable for:

Cs-uc18qkdCs-uc24qkdCu-uc12qkdCu-uc18qkdCu-uc24qkd