gefran 40F 96 Quick Start Manual page 4

Configurable frequency indicator - interceptor

Advertisement

• Input parameters
In
Input settings
Input
configuration
Frequency meter
operating mode
With FP = 0 or 2: Period corresponds to
minimum frequency in input
With FP = 1 or 3: Sampling time,
TC = 0 update after 32 sec.
Selection of full scale
frequency
Multiplier
Divisor
Main input filter
Decimal point position for
full scale
Determines full scale of retransmitted output and alarms
N.B.: valid only for frequencies with fixed full scale;
automatic shift of Dp for higher frequencies
Selection of digital
input 1
Raise key function
(active only in
P.V.selection)
Lower key function
(active only in
P.V.selection)
Low limit for the alarms
set point
High limit for the alarms
set point
4
0 Frequency - input NPN
1 Frequency - input PNP
2 AC input
0 Normal frequency value
1 Settable sampling time
2 Normal frequency value
with fixed full scale
3 Sampling time settable
with fixed full scale
0.0 ... 10.0sec
Max. frequency
in input
0
1KHz
1
2KHz
2
4KHz
3
10KHz
4 (*)
20KHz
5 (*)
40KHz
6 (*)
80KHz
7 (*)
100KHz
+8 enable MU, dE parameters
(*) value shown indicates frequency /10 see
application example
1 ... 255
1 ... 255
ON / OFF
ON = 100Hz filter
dP
Format
0
XXXX
1
XXX.X
2
XX.XX
3
X.XXX
0
None
1
Zero
2
Hold
3
Flash
4
Max. peak display
5
Min. peak display
6
Delta peak display
7
Peak memory reset
8
Zero + peak
memory reset
9
Alarms reset
10 Peak + alarms reset
11 Zero + alarms
reset
12 Peak + zero +
alarms reset
13 Output status OUT1
14 Output status OUT2
15 Output status OUT3
-1999 ... 9999
-1999 ... 9999
O u
Prescaler
ratio
1
2
4
2
4
8
16
32
P r
+4 to disable In and Ou pages
+8 to disable Cf page
+32 base configuration (the following parameters will not be displayed:
U. C.
• Output parameters
Output settings
Number of outputs
0 to 3
1. t - 2. t - 3. t
Value
Direct
Alarm type 1
(max.)
Inverse
(min.)
0
Direct
1
Inverse
Alarm type 2
2
Direct
3
Inverse
4
Direct
5
Inverse
6
Direct
Alarm type 3
7
Inverse
+8 to disable on power-up until first alarm
+16 to memorize
+32 to filter with F.O. mode (output filter mode)
0 not active: calculated status
Output filter mode
is sent directly to relay
1 On delay (DON)
2 delay activation from
time of deactivation
of output (DBI)
3 Off delay (DOF)
4 Delay for activation
only at power-up
(DPO)
+ 8 time base max. 99 min (default = 99 sec)
delay for F.O.
0 to 99 min or sec
Minimum output pulse
0 to 99 sec
Disabled by setting value 0
Displayed if associated with at least one output
Minimum scale analog
-1999 ... 9999
repeat output
Maximum scale analog
-1999 ... 9999
repeat output
• Protection
Value
Displayed
Protection code
parameters
0
o.1, o.2, o.3
1
o.1, o.2
2
3
In: FI, L_L, H_L
Ou: On [forced to no. outputs present])
• User Calibration
U.C.
CPU F Function
1
analog retransmission
output
Calibration of
minimum (*)
Calibration of
(*) when U.C. = 1 press keys
maximum (*)
analog output
81671B_MHW_40F96_0308_ENG
Absolute
Normal
Relative to Symmetrical
previous
(window)
Absolute
Normal
Absolute
Normal
Relative
Normal
Relative
Normal
Absolute
Symmetrical
Absolute
Symmetrical
Relative
Symmetrical
Relative
Symmetrical
Modifiable
parameters
o.1, o.2, o.3
o.1, o.2
o.1
o.1
o.1
none
∆ ∇
to calibrate