Safety Function And Safe State - Pepperl+Fuchs HiC283 Series Manual

Functional safety switch amplifier
Table of Contents

Advertisement

Functional Safety HiC283*
Planning
3.3

Safety Function and Safe State

Safe State
The safe state of output I and output II is the high impedance state or the fault state.
Safety Function
HiC2831*
Switch
Output I and output II
S1
S1
Table 3.1
HiC2832*
Switch
Channel I
S1
S1
Channel II
S3
S3
Table 3.2
12
Position
Function
II
Normal mode of
operation
I
Inverse mode of
operation
Switch settings HiC2831*
Position
Function
II
Normal mode of
operation
I
Inverse mode of
operation
II
Normal mode of
operation
I
Inverse mode of
operation
Switch settings HiC2832*
If a low current is present at input I,
output I and output II are high impedant
(safe state).
If a high current is present at input I,
output I and output II are high impedant
(safe state).
If a low current is present at input I,
output I is high impedant (safe state).
If a high current is present at input I,
output I is high impedant (safe state).
If a low current is present at input II,
output II is high impedant (safe state).
If a high current is present at input II,
output II is high impedant (safe state).

Advertisement

Table of Contents
loading

Table of Contents