Additionally, the following parts may belong to the documentation, if applicable: • EU-type examination certificate • EU declaration of conformity • Attestation of conformity • Certificates • Control drawings • FMEDA report • Assessment report • Additional documents For more information about Pepperl+Fuchs products with functional safety, see www.pepperl-fuchs.com/sil.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Introduction Safety Information Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Product Description Product Description Function General This isolated barrier is used for intrinsic safety applications. The device transfers digital signals from SN/S1N safety sensors or approved dry contacts from the explosion-hazardous area to the non-explosion-hazardous area.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Product Description Interfaces The device has the following interfaces: • Safety relevant interfaces: input, output I, output II • Non-safety relevant interfaces: power supply, fault output Note For corresponding connections see datasheet. Marking Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany...
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Planning Planning System Structure 3.1.1 Low Demand Mode of Operation If there are two control loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Planning Assumptions The following assumptions have been made during the FMEDA: • The collective error message output is not considered in the FMEDA and in the calculations. • Failure rate based on the Siemens standard SN 29500.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Planning Safety Function and Safe State Safe State The safe state is reached when the input goes to the low current state (I < 2.1 mA) or the fault state (I > 5.9 mA). Safety Function HiC2853R1, HiC2853R4 The safe state for the resistive transistor output (output I) is the high impedant state.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Planning Characteristic Safety Values Parameters Characteristic values Assessment type and Full assessment documentation Device type Demand mode Low demand mode or high demand mode Safety function Signal transfer via electronic output Signal transfer via resistive...
As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime. Our experience has shown that the useful lifetime of a Pepperl+Fuchs product can be higher if the ambient conditions support a long life time, for example if the ambient temperature is significantly below the maximum ambient temperature.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Mounting and Installation Mounting and Installation Mounting and Installing the Device Observe the safety instructions in the instruction manual. Observe the information in the manual. Observe the requirements for the safety loop. Connect the device only to devices that are suitable for this safety application.
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation Operation Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. • Do not bypass the safety function.
Page 17
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation 5.1.1 HiC2853R1 Equipment required: • Digital multimeter with an accuracy of 0.1 % Use for the proof test of the intrinsic safety side of the device a special digital multimeter for intrinsically safe circuits.
Page 18
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation Device fault HiC2853R1 2 k 24 V 8.0 mA < I < 9.2 mA 0.46 mA < I < 0.62 mA I < 0.05 mA fault Table 5.1 Output values for HiC2853R1 HiC2853R1 Multimeter...
Page 19
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation 5.1.2 HiC2853R4 Equipment required: • Digital multimeter with an accuracy of 0.1 % Use for the proof test of the intrinsic safety side of the device a special digital multimeter for intrinsically safe circuits.
Page 20
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation Device fault HiC2853R4 10.0 mA 4.58 V < U < 4.85 V 13.3 V < U < 14.35 V < 0.05 mA fault Table 5.2 Output values for HiC2853R4 HiC2853R4 Multimeter ( I )
Page 21
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation 5.1.3 HiC2853R6 Equipment required: • Digital multimeter with an accuracy of 0.1 % Use for the proof test of the intrinsic safety side of the device a special digital multimeter for intrinsically safe circuits.
Page 22
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 Operation U at terminal 11 fault 23.4 V 14.7 V < U < 15.6 V 6.2 V < U < 6.8 V < 0.2 V fault Table 5.3 Measured values for HiC2853R6 Note As an alternative to a 2nd power supply, the operating voltage of the termination board can also be bridged to terminal 11.
Report all failures in the safety function that are due to functional limitations or a loss of device function – especially in the case of possible dangerous failures. In these cases, contact your local sales partner or the Pepperl+Fuchs technical sales support (service line).
Functional Safety HiC2853R1, HiC2853R4, HiC2853R6 List of Abbreviations List of Abbreviations Emergency Shutdown Failure In Time in 10 Failure Mode, Effects, and Diagnostics Analysis FMEDA Probability of safe failure Probability of dangerous detected failure Probability of dangerous undetected failure ...