Assumptions

The following assumptions have been made during the FMEDA:
Failure rate based on the Siemens standard SN 29500.
Failure rates are constant, wear is not considered.
External power supply failure rates are not included.
Only one input and one output are part of the safety function (only for 2-channel version).
The safety-related device is considered to be of type A device with a hardware fault
tolerance of 0.
The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time of
40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates must
be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
The indication of a dangerous failure (via fault bus) is detected within 1 hour
by the programmable logic controller (PLC).
SIL 2 Application
The device shall claim less than 10 % of the total failure budget for a SIL 2 safety loop.
For a SIL 2 application operating in low demand mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
hence the maximum allowable PFD
For a SIL 2 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10
would then be 10
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 60 % according to table 2 of IEC/EN 61508-2 for a SIL 2 (sub) system.
3.3

Safety Function and Safe State

Safe State
The safe state is the de-energized state of the outputs, independent of the mode of operation.
Safety Function
The safety function has 2 modes of operation:
normal operation (output follows input)
inverted operation (output inverts input)
The 1-channel devices have 2 outputs where output II may be used in safety-relevant
applications if output II is configured to follow output I.
Use the following DIP switch settings for safety-related applications:
12
value would then be 10
avg
-6
per hour, hence the maximum allowable PFH value
-7
per hour.
value
avg
-2
,
-3
.