Download Print this page
Pepperl+Fuchs HiD2844 Manual

Pepperl+Fuchs HiD2844 Manual

Switch amplifier

Advertisement

Quick Links

Switch Amplifier
Features
• 4-channel isolated barrier
• 24 V DC supply (bus powered)
• Dry contact or NAMUR inputs
• 4 passive transistor outputs
• Line fault detection (LFD)
• Up to SIL2 acc. to IEC 61508
Function
This isolated barrier is used for intrinsic safety applications. It
transfers digital signals (NAMUR sensors/mechanical
contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a passive transistor for
the safe area load. The module output changes state when the
input signal changes state. The normal output state can be
reversed with the selector switches on the side of the unit.
Line fault detection (LFD) can be selected or disabled via a
selector switch.
During an error condition, the transistor reverts to its de-
energized state and the LEDs indicate the fault. A separate
fault output bus is available. The fault conditions can be
monitored via a Fault Indication Board.
This module mounts on a HiD Termination Board.
Connection
I
II
III
IV
Zone 0, 1, 2
Div. 1, 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
SL2
1.5 kΩ
+
1
5a
10 kΩ
-
4
5b
1.5 kΩ
+
2
1a
10 kΩ
-
5
1b
1.5 kΩ
+
3
3a
10 kΩ
-
6
3b
1.5 kΩ
+
7
7a
10 kΩ
-
8
7b
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Assembly
Front view
LEDs red:
Line fault
channel 1 ... 4
Switch 1 ... 8
HiD2844
SL1
8a
11
7a
14
10a
12
9a
15
9b
13
10b
16
8b
17
7b
18
1a, 1b
2a, 2b
6b
Termination Board
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
HiD2844
LED green:
Power supply
PWR
LEDs yellow:
FAULT
STATUS
Status output
CH 1
channel 1 ... 4
CH 2
CH 3
CH 4
HiD
2844
Place for
labeling
2
+
I
-
+
II
-
+
III
-
+
IV
-
-
24 V DC
+
FAULT
1

Advertisement

loading

Summary of Contents for Pepperl+Fuchs HiD2844

  • Page 1 24 V DC 2a, 2b FAULT Zone 0, 1, 2 Termination Board Div. 1, 2 Refer to "General Notes Relating to Pepperl+Fuchs Product Information". Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com...
  • Page 2 EN 60079-11: 2007, voltage peak value 375 V Directive conformity Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006 Refer to "General Notes Relating to Pepperl+Fuchs Product Information". Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 www.pepperl-fuchs.com...
  • Page 3 Input OPEN/Transistor OPEN Lead fault detection LFD disable Channel 3 and 4 (switch 5 ... 8) only for HiD2844. Configure the device in the following way: • Push the red Quick Lok Bars on each side of the device in the upper position.