FlowCon Green 15-40 mm (1/2"-1 1/2")
1B95092 - 10/2021
Installation and Operation Instruction
The FlowCon Green inserts are for use with
three different FlowCon valve housings, either:
FlowCon A DN15-25 (1/2"-1")
FlowCon AB DN15-32 (1/2"-1 1/4")
FlowCon ABV DN15-40 (1/2"-1 1/2")
Insert Setting and Installation
Prior to installing the FlowCon Green insert (sup-
plied from factory in setting 5.0 due to calibra-
tion), the system should be properly flushed.
Blank valve covers are available to be installed
during flushing.
It is recommended to grease the O-rings located
around the insert and headnut with silicone grease
before installing the insert in the valve housing.
General Assembly Drawing
FlowCon Green
A: Valve housing
B: Green insert
C: Adjustment keys
D1: P/t plug (2 pcs.)
D2: Plug (2 pcs.)
E: Union end connections
F: FlowCon actuator
This paper is a supplement to the FlowCon General Instruction
Latest release of any FlowCon material is available on www.flowcon.com
Figure 1
The desired flow rate is set by adjusting the
insert (turn counter-clockwise to setting 1.0 and
then clockwise up) with a special adjustment
key. Range is between 1.0 and 5.0.
⚠ Do not overturn.
Scale setting is located on top of
the insert. For Green.0, Green.1 and
Green.2, large white digits, numbered
1 to 5, indicate full turns and red digits,
numbered 0 to 9, indicate 1/10 of full
turn. For Green.1HF scale is op-
posite. Here large green digits, num-
bered 0 to 9, indicate 1/10 of full
turn and black digits, numbered 0 to
5, indicate full turn. Flow setting may
be done either before or after the in-
sert is installed in the valve housing.
Once flow is set and insert is fitted in the valve
housing, the required actuator may be applied.
Please see specific installation instruction for
selected actuator.
Turn to
higher
settings
C
D1
D2
E
A
F
B
E
Page 1 of 2