FlowCon SH series Installation And Operation Instruction

15-40mm, 1/2 inch -1 1/2 inch. externally adjustable dynamic balancing valve

Advertisement

Quick Links

FlowCon SH 15-40mm
INSTALLATION AND OPERATION INSTRUCTION
FlowCon SH
Install the
the supply or return pipe work for the unit.
It is recommended that a strainer be installed
prior to the valve body to prevent damage
or blockage due to debris. INSTALL THE
VALVE
HOUSING
DIRECTIONAL
ARROW
THE CORRECT DIRECTION.
The valve body is available with double union
end connections, i.e. figure 1.
Two types of end connections are available
for use with the union nut:
Threaded (male or female):
The thread standard is ISO 228, which is a
straight metric thread (compatible with BS-
2779) or NPT threading standard, depending
on the end connections ordered. The threads
on both the connection and piping should
be cleaned carefully. As these models are
union end connected, the union nuts and
the end connections should be removed for
installation.
O-rings
are
supplied
body and used to seal the connections.
It is recommended to grease the o-rings
with a silicone grease before installation.
IMPORTANT: Never use mineral oil or petrol
based grease or oil on the o-rings. Please
make sure these are in place in the
o-ring grooves in the inlet and outlet of the
valve body, when installing the housing and
REMEMBER TO TIGHTEN THE UNION
NUTS TO ENSURE SEALING.
1A95000
FlowCon SH 15-40mm, 1/2"-1 1/2"
valve either in
WITH
THE
FLOW
POINTING
with
the
Denmark
For all threaded connections please clear
threads on both valve and piping of debris.
Sealant such as pipe dope or teflon tape is
recommended. WHEN USING HEMP AS
PIPE SEALANT, ENSURE NO STRANDS
ARE LEFT IN THE VALVE OR PIPING.
IN
Soldered end (sweat):
REMOVE THE END CONNECTIONS FROM
THE HOUSING BEFORE SOLDERING. THIS
ENSURES
INTERNAL PARTS ARE NOT DAMAGED
BY HEAT.
Valve bodies are as standard supplied
with body tappings plugged.
Alternatively, the valve body can be ordered
with pressure/temperature fittings (p/t plugs)
for the body tappings. Before finger mount-
ing the p/t plugs in the body tappings,
please seal the threads of the p/t plugs.
(DO NOT OVER TIGHTEN).
Figure 1
valve
Dubai
- 1 -
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
EXTERNALLY ADJUSTABLE
DYNAMIC BALANCING VALVE
THAT
THE
O-RINGS
DN
15/20/25
Singapore
AND
USA
10/2008

Advertisement

loading

Summary of Contents for FlowCon SH series

  • Page 1 REMEMBER TO TIGHTEN THE UNION NUTS TO ENSURE SEALING. Denmark Dubai Singapore 1A95000 10/2008 - 1 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 2 Warranty obligation. Failure to abide by all recommendations this installation operation instruction will void warranty. Denmark Dubai Singapore 1A95000 10/2008 - 2 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 3: Flow Rate

    ±5% of controlled flow rate or 0.69 2491 11.0 1.93 6934 30.5 ±2% of maximum flow rate. 0.70 2520 11.1 1.95 7020 30.9 Denmark Dubai Singapore 1A95000 10/2008 - 3 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 4 Micrometer setting Adjustment key P/t plug (2 pcs.) Plug and gasket (2 of each) Union end connections. Figure 2 DN15/20 Denmark Dubai Singapore 1A95000 10/2008 - 4 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.