FlowCon UniQ Installation And Operation Instruction

Temperature control and automatic balancing valve

Advertisement

Quick Links

FlowCon UniQ
INSTALLATION AND OPERATION INSTRUCTION
Install the FlowCon UniQ as called for in the
design drawings. Although the performance of
the valve is not affected either way, industry
standards call for balancing devices to be in-
stalled on the downstream side of the terminal
unit. INSTALL THE VALVE WITH THE FLOW
DIRECTIONAL ARROW POINTING IN THE
CORRECT DIRECTION.
The FlowCon UniQ is available with fixed
20mm male ISO threaded connections fittable
for DN15 EuroCone according to EN215, Annex
A, i.e. figure 1.
FlowCon UniQ is similarly available with female-
by-female threaded connections DN15 or DN20,
i.e. figure 2.
Figure 1
For all threaded connections please clear threads
on both valve and piping of debris. Sealant such
as pipe dope or teflon tape is recommended on
thread sealings.
WHEN USING HEMP AS PIPE SEALANT,
ENSURE NO STRANDS ARE LEFT IN THE
VALVE OR PIPING.
EuroCone fittings should seal with UniQ housing
without extra sealant.
1B95038
FlowCon UniQ 15-20mm
Figure 2
Denmark
Dubai
AND AUTOMATIC BALANCING VALVE
Setting the valve:
The desired flow rate is chosen by adjusting the
valve (turned from setting 1.0 and up), with a
special designed key for a rough setting of the
valve (figure 3) or a large FlowCon adjustment
wheel for a micrometer setting (figure 4). There is
only one correct way to place the wheel on the
valve. Make sure there is no gap between the
wheel and the FlowCon UniQ.
Figure 3
The key or wheel are used to adjust the scale
on the top of the valve. Position is defined by
a "dot" marked on the edge of the housing top.
Once the correct flow rate has been selected,
the actuator can be applied. Please see spe-
cific installation instruction for selected actuator.
It is important to adjust the valve accord-
ing to the setting needed BEFORE pressure
is applied to the system.
USA
Brasil
- 1 -
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
TEMPERATURE CONTROL
Figure 4
Singapore
www.flowcon.com
01/2014

Advertisement

loading

Summary of Contents for FlowCon UniQ

  • Page 1 ENSURE NO STRANDS ARE LEFT IN THE VALVE OR PIPING. EuroCone fittings should seal with UniQ housing without extra sealant. Denmark Dubai Brasil Singapore www.flowcon.com 1B95038 01/2014 - 1 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 2 Accuracy: Greatest of either ±10% of controlled flow rate or ±5% of maximum flow rate. 0.2015 3.192 0.2086 3.305 Note 1: Min. ΔP=10 x √setting Denmark Dubai Brasil Singapore www.flowcon.com 1B95038 01/2014 - 2 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 3 Ensure that the valve is not in the fully closed position when filling the system with water. Denmark Dubai Brasil Singapore www.flowcon.com 1B95038 01/2014 - 3 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
  • Page 4 FlowCon UniQ TEMPERATURE CONTROL AND AUTOMATIC BALANCING VALVE Denmark Dubai Brasil Singapore www.flowcon.com 1B95038 01/2014 - 4 - FlowCon International assumes no responsibility for mistakes, if any, in any printed material.