FlowCon SM 50-250mm Installation And Operation Instruction Manual

Advertisement

Quick Links

FlowCon SM 50-250mm
INSTALLATION AND OPERATION INSTRUCTION
Install the FlowCon SM valve either in the sup-
ply or return pipework for the unit. It is recom-
mended that a strainer be installed prior to the
valve body to prevent damage or blockage
due to debris.
INSTALL THE VALVE HOUSING WITH THE
FLOW DIRECTIONAL ARROW POINTING IN
THE CORRECT DIRECTION.
The valve body is available for double flange
connections, i.e figure 1.
Figure 1
FlowCon SM 50-250mm, 2"-10"
Denmark
DYNAMIC SELF BALANCING
O-rings are supplied with the valve body and
are used to seal the connections. Please make
sure these are in place in the o-ring grooves
in the inlet and outlet of the valve body, when
installing the housing.
FlowCon SM.6 (200-250mm) contains two
o-ring grooves (figure 2). Sealing is done on
smallest diameter groove if 200mm flanges
are used and on the largest diameter groove if
250mm flanges are used.
O-ring Groove
200mm flanges
O-ring Groove
250mm flanges
Figure 2
It is recommended to grease the o-rings with a
silicone grease before installation.
IMPORTANT: Never use mineral oil or petrol
based grease or oil on the o-rings.
Valve bodies are as standard supplied with
pressure/temperature fittings (p/t plugs).
Before finger mounting the p/t plugs in the
body tappings, please seal the threads of the
p/t plugs (DO NOT OVER TIGHTEN).
Dubai
USA
- 1 -
CONTROL VALVE
Singapore
www.flowcon.com
1A95106 - 08/2016
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.

Advertisement

Table of Contents
loading

Summary of Contents for FlowCon SM 50-250mm

  • Page 1 CONTROL VALVE INSTALLATION AND OPERATION INSTRUCTION FlowCon SM 50-250mm, 2”-10” Install the FlowCon SM valve either in the sup- O-rings are supplied with the valve body and ply or return pipework for the unit. It is recom- are used to seal the connections. Please make...
  • Page 2 Snap ring  “Actuator legs” Snap ring: Figure 3 Figure 4 Figure 5 Stop points 360º Figure 6 Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 2 - for mistakes, if any, in any printed material.
  • Page 3: Wiring Instructions

    5/6 of fully open. Lower part of display will show “FLUSH” until control signal is detected. Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 3 - for mistakes, if any, in any printed material.
  • Page 4: Programming Menu

    • 2-10VDC for VDC SELECT CONTROL SIGNAL • 4-20mA for mA • Digital for 2 position or 3 point floating. Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 4 - for mistakes, if any, in any printed material.
  • Page 5 3. Actuator shuts off. If power supply is restored during action 1. or 2., failsafe mode is deactivated. Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 5 - for mistakes, if any, in any printed material.
  • Page 6 If display shows “NA” instead of current flow rate, it indicates that the flow rate is below minimum defined flow rate according to tech note, or that valve model has not been chosen in programming menu step 2. Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 6 - for mistakes, if any, in any printed material.
  • Page 7: Alarm Menu

    The error code will be available in the information in the upper part of the display and the alarm menu. Denmark Dubai Singapore www.flowcon.com 1A95106 - 08/2016 FlowCon International assumes no responsibility - 7 - for mistakes, if any, in any printed material.
  • Page 8: Manual Override

    1. Turn off power to the actuator. For latest updates please see www.flowcon.com 2. Remove actuator from valve as described. 3. Turn spindle to the relevant position (Clock- wise to close valve, counter clockwise to open valve).

Table of Contents