FlowCon SM 50-250mm
INSTALLATION AND OPERATION INSTRUCTION
Install the FlowCon SM valve either in the sup-
ply or return pipework for the unit. It is recom-
mended that a strainer be installed prior to the
valve body to prevent damage or blockage
due to debris.
INSTALL THE VALVE HOUSING WITH THE
FLOW DIRECTIONAL ARROW POINTING IN
THE CORRECT DIRECTION.
The valve body is available for double flange
connections, i.e figure 1.
Figure 1
FlowCon SM 50-250mm, 2"-10"
Denmark
DYNAMIC SELF BALANCING
O-rings are supplied with the valve body and
are used to seal the connections. Please make
sure these are in place in the o-ring grooves
in the inlet and outlet of the valve body, when
installing the housing.
FlowCon SM.6 (200-250mm) contains two
o-ring grooves (figure 2). Sealing is done on
smallest diameter groove if 200mm flanges
are used and on the largest diameter groove if
250mm flanges are used.
O-ring Groove
200mm flanges
O-ring Groove
250mm flanges
Figure 2
It is recommended to grease the o-rings with a
silicone grease before installation.
IMPORTANT: Never use mineral oil or petrol
based grease or oil on the o-rings.
Valve bodies are as standard supplied with
pressure/temperature fittings (p/t plugs).
Before finger mounting the p/t plugs in the
body tappings, please seal the threads of the
p/t plugs (DO NOT OVER TIGHTEN).
Dubai
USA
- 1 -
CONTROL VALVE
Singapore
www.flowcon.com
1A95106 - 08/2016