Download Print this page

FlowCon AHU Wafer Installation And Operation Instruction

Pre-set automatic balancing valves 50-80 mm, 2"-3"

Advertisement

Quick Links

FlowCon AHU Wafer 50-80mm
INSTALLATION AND OPERATION INSTRUCTION
FlowCon AHU Wafer
Install the
for in the design drawings. INSTALL THE AHU
WAFER HOUSING WITH THE FLOW DIREC-
TIONAL ARROW POINTING IN THE CORRECT
DIRECTION.
FlowCon AHU Wafer
The
F386.X.X.B) is available for end connections of
DIN steel flanges from PN10 and up. For valve
sizes 2½" and 3" ANSI steel flanges from class
150 and up are available and for size 2" ANSI
steel flanges class 300 are to be used. Flanges
are not supplied by FlowCon.
Extended pressure/temperature fittings (p/t
plugs) are included as standard. Before finger
mounting the p/t plugs in the body tappings, pls.
seal the threads of the p/t plugs (DO NOT OVER
TIGHTEN).
Assembly drawing
FlowCon AHU Wafer
AHU Wafer housing
O-ring
3" Stainless steel insert (optional)
Retainer clip
Extended p/t plug (2 pcs.).
FlowCon AHU Wafer 50-80mm, 2"-3"
as called
(Model Nos.
Denmark
AUTOMATIC BALANCING VALVE
Inserting the insert:
For FlowCon AHU Wafer bodies size DN50-
DN80 (figure 1), a 3" stainless steel insert (either
standard flow or high capacity) is available. It is
recommended that the o-ring located around the
insert is lubricated with silicone grease, before
the insert is installed into the valve body.
IMPORTANT:
Never use mineral oil or petrol based grease or
oil on the o-ring.
When inserting the insert, be assured to check
the placement of the o-ring. There is no need to
use tools - the insert can be inserted/removed
by the fingers. Once the insert is installed in the
valve body, the retainer clip is fitted to hold the
insert in proper place.
Dubai
USA
- 1 -
WITH PRE-SET INSERT
Figure 1
Singapore
www.flowcon.com
1W95000 - 04/2016
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.

Advertisement

loading

Summary of Contents for FlowCon AHU Wafer

  • Page 1 Install the as called for in the design drawings. INSTALL THE AHU For FlowCon AHU Wafer bodies size DN50- WAFER HOUSING WITH THE FLOW DIREC- DN80 (figure 1), a 3” stainless steel insert (either TIONAL ARROW POINTING IN THE CORRECT standard flow or high capacity) is available.
  • Page 2 FlowCon. Warranty obligation Failure to abide by all recommendations as per this installation and operation instruction will void warranty. For latest updates please see www.flowcon.com Denmark Dubai Singapore www.flowcon.com 1W95000 - 04/2016...
  • Page 3 FlowCon AHU Wafer 50-80mm AUTOMATIC BALANCING VALVE WITH PRE-SET INSERT Stainless Steel Insert Stainless Steel Insert for DN50/65/80, 2”-3” for DN50/65/80, 2”-3” (3” insert, standard flow) (3” insert, standard flow) Type 1 Type 2 Type 4 Type 8 Type 1...
  • Page 4 FlowCon AHU Wafer 50-80mm AUTOMATIC BALANCING VALVE WITH PRE-SET INSERT Denmark Dubai Singapore www.flowcon.com 1W95000 - 04/2016 FlowCon International assumes no responsibility - 4 - for mistakes, if any, in any printed material.