FlowCon AHU Wafer 50-80mm
INSTALLATION AND OPERATION INSTRUCTION
FlowCon AHU Wafer
Install the
for in the design drawings. INSTALL THE AHU
WAFER HOUSING WITH THE FLOW DIREC-
TIONAL ARROW POINTING IN THE CORRECT
DIRECTION.
FlowCon AHU Wafer
The
F386.X.X.B) is available for end connections of
DIN steel flanges from PN10 and up. For valve
sizes 2½" and 3" ANSI steel flanges from class
150 and up are available and for size 2" ANSI
steel flanges class 300 are to be used. Flanges
are not supplied by FlowCon.
Extended pressure/temperature fittings (p/t
plugs) are included as standard. Before finger
mounting the p/t plugs in the body tappings, pls.
seal the threads of the p/t plugs (DO NOT OVER
TIGHTEN).
Assembly drawing
FlowCon AHU Wafer
AHU Wafer housing
O-ring
3" Stainless steel insert (optional)
Retainer clip
Extended p/t plug (2 pcs.).
FlowCon AHU Wafer 50-80mm, 2"-3"
as called
(Model Nos.
Denmark
AUTOMATIC BALANCING VALVE
Inserting the insert:
For FlowCon AHU Wafer bodies size DN50-
DN80 (figure 1), a 3" stainless steel insert (either
standard flow or high capacity) is available. It is
recommended that the o-ring located around the
insert is lubricated with silicone grease, before
the insert is installed into the valve body.
IMPORTANT:
Never use mineral oil or petrol based grease or
oil on the o-ring.
When inserting the insert, be assured to check
the placement of the o-ring. There is no need to
use tools - the insert can be inserted/removed
by the fingers. Once the insert is installed in the
valve body, the retainer clip is fitted to hold the
insert in proper place.
Dubai
USA
- 1 -
WITH PRE-SET INSERT
Figure 1
Singapore
www.flowcon.com
1W95000 - 04/2016
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.