FlowCon EVS insert
INSTALLATION AND OPERATION INSTRUCTION
FlowCon EVS
The
three different FlowCon valve housings, either
FlowCon A, FlowCon AB or FlowCon ABV1.
Install the selected valve housing as called for in
the design drawings. Although the performance
of the valve is not affected either way, industry
standards call for balancing devices to be in-
stalled on the downstream side of the terminal
unit. Especially for the ABV1 with its isolation
ball valve, it is recommended to ensure the iso-
lation valve is downstream of the balancing
device. INSTALL THE VALVE HOUSING WITH
THE FLOW DIRECTIONAL ARROW POINTING
IN THE CORRECT DIRECTION.
FlowCon A
The
A20.X and A25.I.K) is available with fixed female-
by-female threaded connections, i.e. figure 1.
Figure 1
The thread standard for the A model is either
ISO 228, which is a straight metric thread
(compatible with BS-2779) or NPT threading
standard, depending on the product number
ordered.
For all threaded connections pls. clear threads
on both valve and piping of debris. Sealant such
as pipe dope or teflon tape is recommended.
1D95011
FlowCon EVS insert
plug-in insert is for use with
valve (Model Nos. A15.X,
Denmark
TEMPERATURE CONTROL VALVE
WHEN USING HEMP AS PIPE SEALANT,
ENSURE NO STRANDS ARE LEFT IN THE
VALVE OR PIPING.
FlowCon AB
The
AB20.X and AB25.I.K) is similarly available with
fixed female-by-female threaded connections,
i.e. figure 2.
The thread standard for the AB model is equal
to what is available for the A model.
For all threaded connections pls. clear threads
on both valve and piping of debris. Sealant such
as pipe dope or teflon tape is recommended.
WHEN USING HEMP AS PIPE SEALANT,
ENSURE NO STRANDS ARE LEFT IN THE
VALVE OR PIPING.
Pressure/temperature fittings (p/t plugs) are
available upon request for the AB valve. Before
finger mounting the p/t plugs in the body
tappings, pls. seal the threads of the p/t plugs
(DO NOT OVER TIGHTEN).
Alternatively to p/t plugs, the valve body can be
ordered with plugs for the body tappings. Each
plug is sealed by a gasket.
Dubai
USA
Brasil
- 1 -
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
DYNAMIC BALANCED
valve (Model Nos. AB15.X,
Singapore
www.fl owcon.com
Figure 2
04/2012