Download Print this page
Carel iaq+ Quick Start Manual
Hide thumbs Also See for iaq+:

Advertisement

Quick Links

+04U000015- rel. 1.0 - 09.24.2020
iaq
remote monitoring system
+
Installation guide and quick start
WARNINGS
DANGER OF ELECTRIC SHOCK: the device contains live electrical components. Do
not attempt to open the iaq+ box in anyway without disconnecting the main power
supply.
DANGER: The installation, operation and maintenance must be performed in
compliance with the instructions provided in the manual and with all legal
requirements in force. All other uses and modificiations to the device that are not
authorized by CAREL are considered improper.
1.
INTRODUCTION
The iaq+ is the CAREL solution for the monitoring and
management of indoor air quality. The iaq+ system allows
continuous control of indoor conditions, acquiring all the
data needed to maintain an ideal environment.
Dimensions
Length
Inches (mm)
4.63 (117.5)
117.500
4.63
47.500
1.87
36.718
1.45
24.595
0.97
52.103
2.05
90.000
3.54
2.
SINGLE ZONE SETUP
No setup is required for a stand-alone, single zone iaq+
monitor. The c.pco mini controller is pre-installed in the
iaq+ box and sensors are wired internally. All that is
required is to supply power by plugging in the 24 vdc
power supply.
up
Width
Height
7.45 (120)
7.09 (180)
47.500
1.87
180.000
7.09
180.000
7.09
189.173
7.45
Liability for injury or damage caused by incorrect use of the device lies exclusively
with the user. The unit contains live electrical devices and components.
All work pertaining to the unit must only be performed by a specialist and qualified
personnel who are aware of the necessary precautions.
3.
MULTI ZONE SETUP
Multizone applications are designed to use a CAREL boss
mini as the central monitoring system. This requires an iaq+
box in each zone connected by ethernet.
For multiple boxes, it is best to insert a unique name to
identify each box by following these steps:
• Connect a PC to the iaq+ monitor by ethernet port. Use
a browser to access all the information. The iaq+ monitor
defaults to address http://192.168.1.77.
• Adjust your ethernet adapter to the same subnet, for
example:
• Connect an ethernet cable directly from the iaq+ to your
PC.
• Use your browser to go directly to http://192.168.1.77.
You will be at the Home screen. Select gear icon to
access the settings page.
1
+04U000015- rel. 1.1 - 2020.10.08

Advertisement

loading
Need help?

Need help?

Do you have a question about the iaq+ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carel iaq+

  • Page 1 CAREL are considered improper. INTRODUCTION MULTI ZONE SETUP The iaq+ is the CAREL solution for the monitoring and Multizone applications are designed to use a CAREL boss management of indoor air quality. The iaq+ system allows mini as the central monitoring system. This requires an iaq+ continuous control of indoor conditions, acquiring all the box in each zone connected by ethernet.
  • Page 2 It will also be the Local trending and monitoring of several iaq+ units can be new IP hostname. performed using a CAREL boss. The boss system can be scaled up from monitoring 1 device up to 300 devices. See boss information at https://www.carel.com/product/boss.