2.3 I Electricity supply connecti ons (depending on the models)

Incorrectly ti ghtened terminals may cause the terminal unit to heat up and invalidate the
warranty.
• Before any work inside the device, you must cut the electricity supply as there is a risk of
electric shock which may cause material damage, serious injury or even death.
Only a qualifi ed and experienced technician is authorised to carry out cabling in the equipment
or to replace the supply cable.
The exchanger's electrical supply must be provided through a protecti on and circuit breaking device (not supplied)
complying with the standards and regulati ons in force in the country where it is installed.
Electrical protecti on: via 30 mA residual-current circuit breaker.
The electricity supply must correspond to the voltage indicated on the device's informati on plate.
Use the power supply cable delivered with the appliance.
All extension cables or multi socket connects are prohibited. Request the installati on of a protected power socket near
the appliance from an approved technician.
If the supply cable is not long enough, it must be replaced by a qualifi ed technician.
The electricity supply cable must be insulated against any cutti ng or hot elements that may damage or crush it.
The equipment must be connected to an earth socket.
The electrical connecti on lines must be fi xed.
2.3.1 Connecti ng an external command to supply the primary circuit
Use a 3G1 cable (secti on 1 mm²),
This functi on is provided via the dry contact without polarity "normally open at rest" (maximum intensity 5A under
250Vac 50-60Hz) available on the terminal 19-20 regulator,
The wire connected to terminals 19-20 must go through the additi onal discharge "grommet" (supplied) to be installed
on the base of the box.
Connecti on to a heati ng source
Connecti on to a 3-channel valve with
mechanical return
H0360800.D - EN - 2016-02
Connecti on to a circulati ng pump
Connecti on to a motorised 3-channel
valve with two rotati on directi ons
Ph: live
N: neutral
F*: protecti on fuse (maximum
5A)
C*: additi onal circulati ng
pump
V'*: 3-channel valve with
mechanical return
CH*: existi ng heati ng source
V''* : motorised 3-channel
valve with two rotati on
directi ons
KA1*: command relay
* not supplied
EN
7