temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Fast Transient
Dielectric Strength
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RS900GPF
Installation Manual, 01/2021, C79000-G8976-1353-05
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Test
Cold Temperature
Dry Heat
6.2 EMC and Environmental Type Tests
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Description
Test Ad
Test Bd
Vibration
Shock
Certification
Test Levels
± 8 kV
± 15 kV
35 V/m
± 2 kV @ 2.5 kHz
± 1.5 kV
± 2 kV
2.2 kV Common Mode @ 1 MHz
2.2 kV Common and
Differential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
2 kV (Failsafe Relay)
1.5 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
2g @ 10-150 Hz
Class 2
30g @ 11 ms
Class 2
 
 
35