Download Print this page

S+S Regeltechnik PREMASGARD 722 Series Operating Instructions, Mounting & Installation page 12

Dual pressure sensor 2 measuring channels, pressure and differential pressure measuring transducer, incl. connection set, calibratable, with multi-range switching and active output automatic output switching

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
G
®
PREMASGARD
Schematic diagram
LED (Status)
ON DIP
1 2 3
1
OUT 1
OUT 2
Measuring channel 1
Pressure range
Pressure range
Type 7227
Type 7229
0...+1000 Pa
0...+3000 Pa
0...+5000 Pa
0...+7000 Pa
–1000...+1000 Pa
–100...+100 Pa
–3000...+3000 Pa
–200...+200 Pa
–5000...+5000 Pa
–300...+300 Pa
–7000...+7000 Pa
–500...+500 Pa
Mode
Measurement signal filtering
Selectable time interval
10 s (default)
1 s
Note: DIP 8 and 9 are not defined!
Mounting diagram
(A)
722x
AUTO
ZERO
ON DIP
ON DIP
4 5 6
7 8 9
2
3
MODE
U+
1
+UB 24 V AC / 15...36 V DC
Output 1 pressure [Pa]
2
3
Output 2 pressure [Pa]
GND
4
–UB GND
DIP
DIP
1
2
0...+100 Pa
OFF
OFF
O N
0...+200 Pa
OFF
0...+300 Pa
OFF
O N
0...+500 Pa
O N
O N
OFF
OFF
O N
OFF
OFF
O N
O N
O N
DIP
7
OFF
O N
(B)
PREMASGARD
®
722x
1
2
OFFSET
Measuring channel 2
DIP
Pressure range
3
Type 722x
OFF
0...+1000 Pa
OFF
0...+3000 Pa
OFF
0...+5000 Pa
OFF
0...+7000 Pa
O N
–1000...+1000 Pa
O N
–3000...+3000 Pa
O N
–5000...+5000 Pa
O N
–7000...+7000 Pa
(C)
12
Pin assignment
PREMASGARD
(M12)
2
3
5
1
4
1
+UB 24 V AC / 15...36 V DC
2
Output 1 pressure [Pa]
3
Output 2 pressure [Pa]
4
–UB GND
5
Shield
DIP
DIP
DIP
4
5
6
OFF
OFF
OFF
O N
OFF
OFF
OFF
O N
OFF
O N
O N
OFF
OFF
OFF
O N
O N
O N
OFF
OFF
O N
O N
O N
O N
O N
TYPES OF MONITORING:
(A)
Below-atmospheric pressure:
P1 (+) is not connected
but open against atmosphere
P2 (–) connected to inside of duct
(B)
Filter:
P1 (+) connected upstream of filter
P2 (–) connected downstream of filter
(C)
Ventilator:
P1 (+) connected downstream of ventilator
P2 ( – ) connected upstream of ventilator
Pressure connections at the pressure
switch are marked with
P1 (+) for higher pressure and P2 (–) for
lower pressure.
Rev. 2021 - V11
®
722x

Advertisement

loading