Table 14: Function checks
(continued)
Table 15: Final tasks
36
Item
Mechanical operation of the recloser by pulling the lockout
handle:
Recloser opens
C.07
LED next to the Close function button is no longer lit
LED next to the Open function button lights up green
Position indicator on the bottom of the recloser switch unit is
green (open).
Press the Close pushbutton:
C.08
No switching operation shall take place.
Press the Close function button on the control and protection relay
and then press <Enter>:
C.09
No switching operation shall take place.
Push lockout handle back in completely:
Press Close pushbutton or the Close function button on the
control and protection relay and then press <Enter>
Recloser closes
C.10
LED next to the Open function button is no longer lit
LED next to the Close function button lights up red
Position indicator on the bottom of the recloser switch unit is
red.
Switch on miniature circuit breaker CB2:
C.11
At external temperatures of < 95 ºF (35 ºC) the heaters heat up
after approximately one minute.
Item
Adjust the control and protection relay to the desired setting file:
The control and protection relay shows default set in - Group 1
D.01
If necessary, select other group with user-specific parameter
settings.
If applicable, check the voltage and current readings of the
D.02
controller.
Check the date and the time on the controller and correct if
D.03
necessary.
D.04
Set trip counter to zero (at initial installation only).
Delete event memory (at initial installation only):
D.05
If necessary, download events for further documentation.
D.06
Close and latch swing panel.
D.07
Install controller cover and fasten.
D.08
Close and secure three-phase type SDR controller door.
Checklist
Checklist
Notes
Notes