Siemens SDR 15.5 kV Instruction Manual
Hide thumbs Also See for SDR 15.5 kV:

Advertisement

Quick Links

www.usa.siemens.com/reclosers
Instruction manual
Type SDR 15.5 kV to 38 kV three-phase distribution recloser
Installation operation maintenance E50001-F710-A249-V3-4A00
Answers for infrastructure.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SDR 15.5 kV

  • Page 1 Instruction manual Type SDR 15.5 kV to 38 kV three-phase distribution recloser Installation operation maintenance E50001-F710-A249-V3-4A00 Answers for infrastructure.
  • Page 2 50 volts or more, and shall, Siemens reserves the right to make changes at a minimum, be additionally trained in all of in the specifications shown herein or to make...
  • Page 3: Table Of Contents

    Siemens Industry, Inc. The warranty contained in the contract between Annex A 38 – 39 the parties is the sole warranty of Siemens Industry, Inc. Any statements contained herein do not create new warranties or modify the existing warranty.
  • Page 4: Introduction

    Any other use is forbidden, unless the and use of the equipment. consent of Siemens has been obtained. Personnel must familiarize themselves as If the above-mentioned conditions are not early as possible with the instructions and...
  • Page 5 Siemens field service at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S. For medium voltage customer service issues, contact Siemens at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.
  • Page 6: General Description

    General description Recloser principle and design The manufacture, design and testing of the vacuum recloser is based on current Reclosers are used in distribution systems. regulations and standards and state-of-the- Like circuit breakers, reclosers are used to art technology. The product conforms to the make and break normal and fault currents.
  • Page 7 1. Pole with integrated vacuum interrupter 2. Side section with support foot 3. Position indicator (underneath) 4. Operating mechanism housing 5. Lower terminal (usually load side) 6. Upper terminal (usually line side) 7. Ground terminal connection 8. Lockout handle Terminal lugs optional Figure 1: Three-phase recloser switch unit front view 1.
  • Page 8 Pole The sequence of the poles is C - B - A (sequence left to right when viewed from the The poles are molded using cycloaliphatic lower terminal side of the recloser switch unit epoxy resin specially designed for outdoor - front of recloser) (refer to Figure 4).
  • Page 9 Siemens controllers. If a electrically, whether locally or from a remote non-Siemens controller is used, it is the location. The interlocking is not reset until the controller vendor’s obligation to properly...
  • Page 10 Siemens type 7SC80 feeder automation Standard pole frame controller Siemens type 7SJ80 feeder automation controller Figure 9: Typical pole-mounting frames Siemens type 7SJ64 feeder automation HMI controller. Only the Siemens type 7SR224 control and protection relay option is illustrated in this instruction manual.
  • Page 11 Three-phase type SDR controller 1. Door The three-phase type SDR controller is 2. Three-phase type SDR equipped with integrated pole-mount controller brackets. It can be installed on the recloser 3. Pole-mount bracket pole or substation frame at an operating 4. Type 7SR224 control and height as preferred by the user.
  • Page 12 Figure 13: Connector mounting plate, control cable connector, 1. Connector mounting plate voltage sensor connector and 2. Control cable connector optional antenna or auxiliary power connection 3. Optional voltage sensor connector 4. Optional auxiliary power connection 5. Optional antenna connector provision Figure 14: Optional vandal guard 1.
  • Page 13 A. Capacitor discharge switch B. J1 - jumper 1, pins 1-2 C. J2 - jumper 2, pins 1-2 D. J3 - jumper 3, pins 1-2 E. J4 - jumper 4, pins 1-2 Pin position Pin position Figure 17: PCB2 jumpers Hazardous voltage.
  • Page 14 Auxiliary power supply Deep discharge protection (provided with the Siemens type 7SR224 control and The three-phase type SDR controller uses an protection relay) internal 48 V bus, which is backed-up by rechargeable batteries as an uninterruptible The controller is equipped with deep power supply.
  • Page 15: Receiving, Handling And Storage

    Introduction 3. Notify the Siemens field service at +1 (800) 347-6659 or +1 (919) 365- This portion of the manual covers the 2200 outside the U.S.
  • Page 16 Storage procedure Space heating Whenever possible, store the recloser Space heating for the controller must be indoors. The storage environment must be used for both indoor and outdoor storage to clean, dry and free of such items as: prevent condensation and corrosion. The construction dust, corrosive atmosphere, controller space heater should be connected mechanical abuse and rapid temperature...
  • Page 17: Installation And Commissioning

    Installation and commissioning Hazardous voltages. Will cause death, serious injury or property damage. To avoid electrical shock or burns, this equipment must be installed, operated and maintained only by qualified persons thoroughly familiar with the equipment, instruction manuals and drawings. Heavy weight.
  • Page 18 The following preparatory work must be Mechanical installation performed: The following documents are required for Instruct installation and maintenance installation: personnel with regard to: These operating instructions 1. Safety Order specific drawings 2. Cleanliness at installation site Installation and commissioning report form (see page 32).
  • Page 19 Installation of the three-phase type SDR Connection covers controller on the pole The control and (optional) voltage sensor To attach the three-phase type SDR controller cable connections are supplied with covers at the following components are required: the recloser switch unit and controller. When connecting the cables, the covers should be Two 0.75 inch mounting bolts with nuts stored in a clean and dry environment, such...
  • Page 20 1. Recloser switch unit 2. Surge arrester load side (optional) 3. Ground terminal (switch unit) 4. Ground connection for surge arrester (optional) 5. Ground wire 1. Connector for auxiliary power 6. Control cable supply (optional) 7. Three-phase type SDR controller 2.
  • Page 21 Figure 22: Three-phase type SDR controller information in Annex A on page 38. connections on page 20. Only the Siemens type 7SR224 control and protection relay option is illustrated in this instruction manual.
  • Page 22: Operation

    Operation Operation Switching The recloser is just one device in a distribution Switching comprises electrical switching system. The user of the recloser must set the (remote and/or local operation) and controller protection and control parameters mechanical switching (by means of the to suit the user’s distribution system needs, lockout handle).
  • Page 23 Lockout operation Closing the recloser electrically from the controller Lockout operation combines the mechanical tripping / opening of the recloser and the 1. Using a hot stick or suitable rod from the interlocking to inhibit subsequent closing of ground, push the lockout handle back in the recloser.
  • Page 24 Table 2: Troubleshooting Malfunction Remedy The auxiliary power supply is protected by a miniature circuit breaker in the front of the swing panel. Failure of the auxiliary power supply (for example, "Aux power OK" LED 1. Check miniature circuit breaker CB1 and switch on if necessary. does not light up).
  • Page 25: Maintenance

    Maintenance Hazardous voltages. Will cause death, serious injury or property damage. Always de-energize and ground the equipment and all terminals before performing any work near high-voltage conductors. Work on the recloser switch unit or the control cubicle should be performed only by qualified personnel. Do not open the inner panel of the control cubicle, as interior parts energized at voltages higher than 50 V are present.
  • Page 26 Animal guards On request Set of terminal connectors (six pieces) On request Set of batteries (four batteries, 12 Ah, 48 V) On request Heaters On request Type SDR 15.5 kV to 38.0 kV distribution vacuum three-phase recloser E50001-F710-A249-X-XXXX instruction manual...
  • Page 27: Technical Data

    Technical data Characteristic Unit Voltage class Table 5: Main characteristic data Rated maximum voltage U 15.5 27.0 27.0 38.0 Rated continuous current I 630, 800 630, 800 630, 800 630, 800 Rated lightning impulse withstand voltage U Power frequency insulation level withstand test voltage (one minute dry) U Rated symmetrical interrupting current I 12.5, 16...
  • Page 28 Current transformer data Altitude correction factor The current transformer has a ratio of The insulating capability of insulation in air 800 A:1 A. The accuracy is 0.5 VA 5P20 to IEC decreases as the altitude increases due to the 60044-1. reduced air density.
  • Page 29 15.5 kV and Table 10: Switch unit dimensions Rated voltage U 38.0 kV 27.0 kV and weights 46.2 (1,173) x 20.5 (521) 46.2 (1,173) x 20.5 (521) Dimensions: length x width x height in (mm) x 37.9 (962) x 43.2 (1,097) Weight lbs (kg) 309 (139)
  • Page 30 Rated voltage U All voltages Table 11: Controller Dimensions: length x width x height (without in (mm) 18.0 (457) x 14.0 (356) x 36.0 (914) pole-mount brackets) Weight (without batteries) lbs (kg) 150 (67) Figure 31: Controller dimensions in (mm) 1.
  • Page 31 Weight 14. Product type/style 15. Sales order number 16. Sales item number IEEE C37.60 17. Switch type MADE IN USA Order Code 18. Instruction manual code Instruction Manual No. Siemens Industry, Inc. 18-762-111-020 7000 Siemens Road, Raleigh, North Carolina 27591...
  • Page 32: Installation And Commissioning Report

    Installation and commissioning report Installation and commissioning report The installation and commissioning report on the following pages is intended for using and copying as a checklist.
  • Page 33 Installation and commissioning report Type SDR distribution recloser User Siemens Type SDR Location Recloser type Contract number Serial number Rated maximum voltage (kV) Rated continuous current (A) Auxiliary voltage Rated short-circuit current (kA) Answers for infrastructure.
  • Page 34 Compare the correct voltage of the recloser. (For example, compare the rated voltage of the recloser with the system A.07 voltage. Contact Siemens customer service if the voltage is incorrect at +1 (800) 347-6659 or +1 (919) 365-2200 outside the U.S.)
  • Page 35 Table 14: Function checks Item Checklist Notes Switch on miniature circuit breakers: CB1 and CB3 (behind the panel): Start-up of controller is shown on display. "Protection healthy" LED lights green after approximately 30 seconds C.01 Status LED "AuxPower OK" lights up green Status LED "Recloser OK"...
  • Page 36 Table 14: Function checks Item Checklist Notes (continued) Mechanical operation of the recloser by pulling the lockout handle: Recloser opens C.07 LED next to the Close function button is no longer lit LED next to the Open function button lights up green Position indicator on the bottom of the recloser switch unit is green (open).
  • Page 37 Item Checklist Notes Table 16 Other services E.01 Instruction manual available. E.02 Routine test records available. E.03 On-site instruction on recloser/controller. E.04 Order specific drawings are available. E.05 Type 7SR224 quick reference guide available. Table 17: Remarks Name Department Date Signature Table 18: Signatures Technician...
  • Page 38: Annex A

    Annex A Vendor website information: Control and protection relay options for Siemens Distribution Feeder Automation Siemens type 7SR224 recloser control relay (SDFA) include: (standard control and protection relay option) http://www.energy.siemens.com/ Siemens type 7SC80 feeder automation us/en/power-distribution/reclosers/recloser- controller http://siemens.siprotec.de/ controller.htm download_neu/index_e.htm Schweitzer Engineering Laboratories, Inc.
  • Page 40 All product designations may be trade- marks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could vio- late the rights of the owners..