Viessmann VITOPEND 100-W Installation And Service Instructions Manual page 36

10.5 to 24 kw and 13 to 30 kw. gas fired central heating and combi boilers for open flue operation. natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
A Outlet temperature sensor (gas
fired combi boiler)
B Boiler water temperature sensor
C Temperature limiter
1. Boiler water temperature sensor:
Pull the leads from the sensor.
Check the sensor resistance and
compare it with the curve.
Replace the sensor in case of
severe deviation.
!
Please note
The boiler water temperature
sensor is immersed in the
heating water (risk of scald-
ing).
Drain the boiler before repla-
cing the sensor.
36
D Flue gas monitoring sensor
% Cylinder temperature sensor (gas
fired central heating boiler)
2. Temperature limiter:
Check the temperature limiter, if
the burner control unit cannot be
reset after a fault shutdown,
although the boiler water tempera-
ture is below approx. 90 °C.
Pull the leads from the sensor.
Check the continuity of the tem-
perature limiter with a multimeter.
Remove the faulty temperature
limiter.
Coat the replacement tempera-
ture limiter with heat conducting
paste and install it.
To reset, briefly turn rotary selec-
tor "tr" fully clockwise and then
back again. The ignition proce-
dure will then be repeated.