Technical data

Input (DC)
Maximum input power (per MPP Tracker/total)
Rated power
Input voltage range for operation
Maximum input voltage
Nominal voltage
Number of MPP trackers
Total MPP input voltage range
MPP input voltage range with full power
Maximum input current (per MPP Tracker/total)
DC short-circuit current I
SC
Open-circuit voltage V
OC
DC connector panel
Connector type
Number of DC connections
DC cable specifications
Use of external string fuses
Overvoltage category
2)
Surge protection devices
Galvanic isolation
Output (AC)
Maximum apparent power
Maximum active power
Nominal apparent power
Nighttime reactive power supply
Nominal voltage
5)
Nominal current
Maximum current
Frequency range
5)
Adjustment range power factor
Total harmonic distortion
Power consumption in night mode
AC connection
Connector type
Copper cable specifications
Aluminum cable specifications
Overvoltage category
2)
Surge protection devices
Mechanical details
Dimensions (W x H x D)
Weight
Cooling
Mounting options
26
12.7 kW / 110 kW
100 kW
200 to 1000 V
DC
1100 V
1)
DC
610 V
DC
8
200 to 1000 V
DC
at 20 °C: 470 to 860 V
at 30 °C: 470 to 840 V
at 40 °C: 520 to 800 V
30 A / 240 A
50 A per MPP tracker
1000 V
/1100 V
DC
Amphenol H4 connector
16 pairs
4/6 mm
2
No external string fuses required
II
1 or 2 strings per MPPT: No external string fuses required
No
110 kVA
3)
110 kW
3) 4)
100 kVA
3)
60 kVAr
380/400/480 V -20%/+30%, 3 phases + PE (△), 3 phases + N + PE (Y)
160 A
168 A at 380/400 V; 133 A at 480 V
50/60 Hz ± 5 Hz
0.8 cap to 0.8 ind (0.9 cap to 0.9 ind at maximum active power)
<3% at nominal apparent power
<3.5 W
6)
L1, L2, L3, N: Terminal with hexagon socket screw
PE: 1x M8 / 1x M10 threaded bolt with nut, spring washer and washer
70 to 240 mm
2
70 to 240 mm
2
III
Type 2 (EN 61463-11), replaceable
699 × 629 × 264 mm
77 kg
1x fan module containing 4 fans for circulating ambient air, replaceable
2x internal fans for preventing heat buildup, replaceable
suspended (mounting plate included in the scope of delivery)
free-standing (moun ting feet available as an accessory)
Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1.0 EN 2022-01-03
M100A
DC
DC
DC
without damage
DC
M100A
(single wire, multi-wire, fine-wire with wire end sleeve)
(round single wire, round multi-wire, sector shaped)
M100A

Advertisement

Table of Contents
loading

Table of Contents