Input (DC)
Maximum input power (per MPP Tracker/total)
Rated power
Input voltage range for operation
Max. input voltage
Rated voltage
Number of MPP trackers
MPP input voltage range total
Maximum input current (per MPP tracker/total)
Maximum DC short-circuit current I
Open-circuit voltage V
OC
DC connection panel
Connector type
Number of DC connections
DC cable specifications
Use of external string fuses
Overvoltage category
2)
Surge protection devices
Galvanic isolation
Output (AC)
Maximum apparent power
Maximum active power
Rated apparent power
Rated voltage
5)
Rated current
Maximum current
Switch-on current
Maximum interruption current
Frequency range
5)
Power factor adjustment range
Total harmonic distortion
Power consumption in night mode
AC connection
Connector type
Copper cable specification
Aluminum cable specifications
Cable diameter
2)
Overvoltage category
Surge protection devices
7)
Mechanical details
Dimensions (W x H x D)
Weight
Cooling
Installation options
Isolating switches
Installation manual M250HV_112 (RPI254M112000) Product Version 0 EU V1.0 EN 2022-04-11
SC
26 kW/250 kW
250 kW
500 to 1500 V
DC
1)
1600 V
DC
1150 V
DC
12 (6 x 2 DC inputs + 6 x 3 DC inputs)
820 to 1350 V
DC
26 A/312 A
60 A per MPP tracker
1500 V
/1600 V
without damage
DC
DC
Amphenol H4 connector
30 pairs
2
4/6 mm
1 or 2 strings per MPPT: no external string fuses required
3 strings per MPPT: external string fuses required
II
Type 2 (EN 50539-11), replaceable
No
250 kVA
3)
250 kW
3) 4)
250 kVA
3)
800 V -20% / +15%, 3 phases + PE (△),
180.5 A.
180.5 A.
225 A (t < 50 ms)
350 A (t < 180 μs)
50/60 Hz ± 5 Hz
0.8 cap to 0.8 ind
<3% at rated apparent power
6)
<6 W
M12 threaded bolts with nuts
(flexible or multi-stranded)
2
95 to 300 mm
120 to 300 mm
2
(round single wire, round multi-wire, sector
shaped)
4-core: 33 to 77 mm;
III
Type 2 (EN 61463-11), replaceable
993 × 644 × 284 mm
101 ± 2 kg
1 fan module containing 4x fans for circulating ambient air, re-
placeable
3 internal fans for preventing heat buildup, replaceable
suspended (mounting plate included in the scope of delivery)
free-standing (mounting feet available as an accessory)
4 mechanical DC isolating switches