Monitoring And Handling Alarms; Acknowledging Alarms; Filtering Alarms - ABB COM600 Series Operator's Manual

Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS756123
4.7.2.
4.7.3.
4.7.4.
COM600 Station Automation Series
Operator's Guide

Monitoring and handling alarms

To monitor and handle alarms in the substation, click Alarms in the menu bar at the top
of the screen. To view the alarms concerning a specific bay, click on the appropriate
object in the substation tree.
You can also filter the alarms concerning a specific voltage level or bay with the Filter
function.
In the Persisting alarms list you can see active alarms. The Fleeting alarms list displays
a list of inactive unacknowledged alarms. The alarm list is continuously updated to
present the actual state of the alarm signals.
To view the event list, click View events.
Figure 4.7.2-1 An example view of alarms

Acknowledging alarms

Click Ack to indicate that you have registered and identified the alarm. Acknowledging
an alarm does not remove the alarm, but changes the alarm state. An acknowledged
alarm is displayed in blue in the Persisting alarms list. Inactive alarms are displayed in
the Fleeting alarms list.
To acknowledge alarms:
1.
Select the check box of the alarms you want to acknowledge in the Alarms list.
2.
Click Ack on the menu bar.
3.
To acknowledge all alarms at the same time, click Ack all.

Filtering alarms

Filters can be used when you want to display only specific information.
COM615 3.1
alarms.png
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Com615 3.1

Table of Contents